[74] Logic Rule 4 See parameter group 13-4*. If Logic Rule
4 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[75] Logic Rule 5 See parameter group 13-4*. If Logic Rule
5 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[80] SL Digital
Output A
See 13-52 SL Controller Action. The output
will go high whenever the Smart Logic
Action [38] Set dig. out. A high is
executed. The output will go low
whenever the Smart Logic Action [32] Set
dig. out. A low is executed.
[81] SL Digital
Output B
See 13-52 SL Controller Action. The input
will go high whenever the Smart Logic
Action [39] Set dig. out. A high is
executed. The input will go low whenever
the Smart Logic Action [33] Set dig. out. A
low is executed.
[82] SL Digital
Output C
See 13-52 SL Controller Action. The input
will go high whenever the Smart Logic
Action [40] Set dig. out. A high is
executed. The input will go low whenever
the Smart Logic Action [34] Set dig. out. A
low is executed.
[83] SL Digital
Output D
See 13-52 SL Controller Action. The input
will go high whenever the Smart Logic
Action [41] Set dig. out. A high is
executed. The input will go low whenever
the Smart Logic Action [35] Set dig. out. A
low is executed.
[84] SL Digital
Output E
See 13-52 SL Controller Action. The input
will go high whenever the Smart Logic
Action [42] Set dig. out. A high is
executed. The input will go low whenever
the Smart Logic Action [36] Set dig. out. A
low is executed.
[85] SL Digital
Output F
See 13-52 SL Controller Action. The input
will go high whenever the Smart Logic
Action [43] Set dig. out. A high is
executed. The input will go low whenever
the Smart Logic Action [37] Set dig. out. A
low is executed.
[120] Local reference
active
Output is high when 3-13 Reference Site =
[2] Local or when 3-13 Reference Site = [0]
Linked to hand auto at the same time as
the LCP is in [Hand on] mode.
Reference site set
in 3-13 Reference
Site
Local
referenc
e
active
[120]
Remote
reference
active
[121]
Reference site:
Local
3-13 Reference Site
[2]
1 0
Reference site:
Remote
3-13 Reference Site
[1]
0 1
Reference site:
Linked to Hand/
Auto
Hand 1 0
Hand -> off 1 0
Auto -> off 0 0
Auto 0 1
Table 6.10
[121] Remote
reference
active
Output is high when 3-13 Reference Site
=[1] Remote or [0] Linked to hand/auto
while the LCP is in [Auto on] mode. See
above.
[122] No alarm Output is high when no alarm is present.
[123] Start command
active
Output is high when there is an active
Start command (i.e. via digital input bus
connection or [Hand on] or [Auto on]),
and no Stop or Start command is active.
[124] Running
reverse
Output is high when the frequency
converter is running counter clockwise
(the logical product of the status bits
‘running’ AND ‘reverse’).
[125] Drive in hand
mode
Output is high when the frequency
converter is in [Hand on] mode (as
indicated by the LED light above [Hand
on]).
[126] Drive in auto
mode
Output is high when the frequency
converter is in [Hand on] mode (as
indicated by the LED light above [Auto
on]).
[151] ATEX ETR cur.
alarm
Selectable if 1-90 Motor Thermal Protection
is set to [20] or [21]. If the alarm 164
ATEX ETR cur.lim.alarm is active, the
output will be 1.
[152] ATEX ETR freq.
alarm
Selectable if 1-90 Motor Thermal Protection
is set to [20] or [21]. If the alarm 166
ATEX ETR freq.lim.alarm is active, the
output will be 1.
[153] ATEX ETR cur.
warning
Selectable if1-90 Motor Thermal Protection
is set to [20] or [21] ]. If the alarm 163
ATEX ETR cur.lim.warning is active, the
output will be 1.