[154] ATEX ETR freq.
warning
Selectable if 1-90 Motor Thermal Protection
is set to [20] or [21]. If the warning 165
ATEX ETR freq.lim.warning is active, the
output will be 1.
[188] AHF Capacitor
Connect
The capacitors will be turned on at 20%
(hysteresis of 50% gives an interval of
10% - 30%). The capacitors will be discon-
nected below 10%. The off delay is 10s
and will restart if the nominal power goes
above 10% during the delay. 5-80 AHF
Cap Reconnect Delay is used to guarantee
a minimum off-time for the capacitors.
[189] External fan
control
The internal logics for the internal fan
control is transferred to this output to
make it possible to control an external
fan (relevant for HP duct cooling).
5-40 Function Relay
Array [9]
(Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB
113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6]
(MCB 105), Relay 8 [7] (MCB 105), Relay 9 [8] (MCB 105))
Option: Function:
[0] * No operation All digital and relay outputs are
default set to “No Operation”.
[1] Control ready The control card is ready. E.g.:
Feedback from a drive where the
control is supplied by an external 24
V (MCB 107) and the main power to
drive is not detected.
[2] Drive ready Drive is ready to operate. Mains and
control supplies are OK.
[3] Drive rdy/rem ctrl The frequency converter is ready for
operation and is in Auto On mode
[4] Enable / no warning Ready for operation. No start or stop
commands have been applied (start/
disable). No warnings are active.
[5] VLT running Motor is running, and shaft torque
present.
[6] Running / no
warning
Output speed is higher than the
speed set in 1-81 Min Speed for
Function at Stop [RPM] Min Speed for
Function at Stop [RPM]. The motor is
running and no warnings.
[7] Run in range/no
warn
Motor is running within the
programmed current and speed
ranges set in 4-50 Warning Current
Low and 4-53 Warning Speed High.
No warnings.
[8] Run on ref/no warn Motor runs at reference speed. No
warnings.
[9] Alarm An alarm activates the output. No
warnings
5-40 Function Relay
Array [9]
(Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB
113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6]
(MCB 105), Relay 8 [7] (MCB 105), Relay 9 [8] (MCB 105))
Option: Function:
[10] Alarm or warning An alarm or a warning activates the
output.
[11] At torque limit
The torque limit set in 4-16 Torque
Limit Motor Mode or 4-17 Torque
Limit Generator Mode has been
exceeded.
[12] Out of current
range
The motor current is outside the
range set in 4-18 Current Limit.
[13] Below current, low Motor current is lower than set in
4-50 Warning Current Low.
[14] Above current, high Motor current is higher than set in
4-51 Warning Current High.
[15] Out of speed range Output speed/frequency is outside
the frequency range set in
4-52 Warning Speed Low and
4-53 Warning Speed High.
[16] Below speed, low Output speed is lower than the
setting in 4-52 Warning Speed Low
[17] Above speed, high Output speed is higher than the
setting in 4-53 Warning Speed High.
[18] Out of feedb. range Feedback is outside the range set in
4-56 Warning Feedback Low and
4-57 Warning Feedback High.
[19] Below feedback, low Feedback is below the limit set in
4-56 Warning Feedback Low.
[20] Above feedback,
high
Feedback is above the limit set in
4-57 Warning Feedback High.
[21] Thermal warning Thermal warning turns on when the
temperature exceeds the limit either
in motor, frequency converter, brake
resistor, or connected thermistor.
[22] Ready,no thermal W The frequency converter is ready for
operation and there is no over-
temperature warning.
[23] Remote,ready,no TW The frequency converter is ready for
operation and is in Auto On mode.
There is no over-temperature
warning.
[24] Ready, Voltage OK The frequency converter is ready for
operation and the mains voltage is
within the specified voltage range
(see General Specifications section in
Design Guide).
[25] Reverse Logic ‘1’ when CW rotation of the
motor. Logic ‘0’ when CCW rotation
How to Programme the Low Ha... VLT Automation Low Harmonic Drive Operating Instructions
84 MG34O202 - VLT
®
is a registered Danfoss trademark
6
6

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300
CategoryDC Drives
LanguageEnglish

Related product manuals