EasyManuals Logo
Home>Danfoss>DC Drives>VLT AutomationDrive FC 300

Danfoss VLT AutomationDrive FC 300 User Manual

Danfoss VLT AutomationDrive FC 300
169 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #86 background imageLoading...
Page #86 background image
5-40 Function Relay
Array [9]
(Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB
113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6]
(MCB 105), Relay 8 [7] (MCB 105), Relay 9 [8] (MCB 105))
Option: Function:
of the motor. If the motor is not
rotating the output will follow the
reference.
[26] Bus OK Active communication (no time-out)
via the serial communication port.
[27] Torque limit & stop Use in performing a coasted stop
and frequency converter in torque
limit condition. If the frequency
converter has received a stop signal
and is in torque limit, the signal is
Logic ‘0’.
[28] Brake, no brake war Brake is active and there are no
warnings.
[29] Brake ready, no
fault
Brake is ready for operation and
there are no faults.
[30] Brake fault (IGBT) Output is Logic ‘1’ when the brake
IGBT is short-circuited. Use this
function to protect the frequency
converter if there is a fault on the
brake module. Use the digital
output/relay to cut out the main
voltage from the frequency
converter.
[31] Relay 123 Digital output/relay is activated
when Control Word [0] is selected in
parameter group 8-**.
[32] Mech brake ctrl Selection of mechanical brake
control. When selected parameters in
parameter group 2-2* are active. The
output must be reinforced to carry
the current for the coil in the brake.
Usually solved by connecting an
external relay to the selected digital
output.
[33] Safe stop active (FC 302 only) Indicates that the safe
stop on terminal 37 has been
activated.
[36] Control word bit 11 Activate relay 1 by control word
from fieldbus. No other functional
impact in the frequency converter.
Typical application: controlling
auxiliary device from fieldbus. The
function is valid when [0] FC profile
in 8-10 Control Word Profile is
selected.
[37] Control word bit 12 Activate relay 2 FC 302 only) by
control word from fieldbus. No other
5-40 Function Relay
Array [9]
(Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB
113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6]
(MCB 105), Relay 8 [7] (MCB 105), Relay 9 [8] (MCB 105))
Option: Function:
functional impact in the frequency
converter. Typical application:
controlling auxiliary device from
fieldbus. The function is valid when
[0] FC profile in 8-10 Control Word
Profile is selected.
[40] Out of ref range Active when the actual speed is
outside settings in 4-52 Warning
Speed Low to 4-55 Warning Reference
High.
[41] Below reference,
low
Active when actual speed is below
speed reference setting.
[42] Above ref, high Active when actual speed is above
speed reference setting.
[45] Bus ctrl. Controls digital output/relay via bus.
The state of the output is set in
5-90 Digital & Relay Bus Control. The
output state is retained in the event
of bus time-out.
[46] Bus ctrl, 1 if timeout Controls output via bus. The state of
the output is set in 5-90 Digital &
Relay Bus Control. In the event of bus
time-out the output state is set high
(On).
[47] Bus ctrl, 0 if timeout Controls output via bus. The state of
the output is set in 5-90 Digital &
Relay Bus Control. In the event of bus
time-out the output state is set low
(Off).
[51] MCO controlled Active when a MCO 302 or MCO 305
is connected. The output is
controlled from option.
[60] Comparator 0 See parameter group 13-1* (Smart
Logic Control). If Comparator 0 in
SLC is TRUE, the output will go high.
Otherwise, it will be low.
[61] Comparator 1 See parameter group 13-1* (Smart
Logic Control). If Comparator 1 in
SLC is TRUE, the output will go high.
Otherwise, it will be low.
[62] Comparator 2 See parameter group 13-1* (Smart
Logic Control). If Comparator 2 in
SLC is TRUE, the output will go high.
Otherwise, it will be low.
[63] Comparator 3 See parameter group 13-1* (Smart
Logic Control). If Comparator 3 in
How to Programme the Low Ha... VLT Automation Low Harmonic Drive Operating Instructions
MG34O202 - VLT
®
is a registered Danfoss trademark 85
6
6

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300
CategoryDC Drives
LanguageEnglish

Related product manuals