5-40 Function Relay
Array [9]
(Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB
113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6]
(MCB 105), Relay 8 [7] (MCB 105), Relay 9 [8] (MCB 105))
Option: Function:
SLC is TRUE, the output will go high.
Otherwise, it will be low.
[64] Comparator 4 See parameter group 13-1* (Smart
Logic Control). If Comparator 4 in
SLC is TRUE, the output will go high.
Otherwise, it will be low.
[65] Comparator 5 See parameter group 13-1* (Smart
Logic Control). If Comparator 5 in
SLC is TRUE, the output will go high.
Otherwise, it will be low.
[70] Logic rule 0 See parameter group 13-4*(Smart
Logic Control). If Logic Rule 0 in SLC
is TRUE, the output will go high.
Otherwise, it will be low.
[71] Logic rule 1 See parameter group 13-4*(Smart
Logic Control). If Logic Rule 1 in SLC
is TRUE, the output will go high.
Otherwise, it will be low.
[72] Logic rule 2 See parameter group 13-4*(Smart
Logic Control). If Logic Rule 2 in SLC
is TRUE, the output will go high.
Otherwise, it will be low.
[73] Logic rule 3 See parameter group 13-4*(Smart
Logic Control). If Logic Rule 3 in SLC
is TRUE, the output will go high.
Otherwise, it will be low.
[74] Logic rule 4 See parameter group 13-4*(Smart
Logic Control). If Logic Rule 4 in SLC
is TRUE, the output will go high.
Otherwise, it will be low.
[75] Logic rule 5 See parameter group 13-4*(Smart
Logic Control). If Logic Rule 5 in SLC
is TRUE, the output will go high.
Otherwise, it will be low.
[80] SL digital output A
See 13-52 SL Controller Action.
Output A is low on Smart Logic
Action [32]. Output A is high on
Smart Logic Action [38].
[81] SL digital output B
See 13-52 SL Controller Action.
Output B is low on Smart Logic
Action [33]. Output B is high on
Smart Logic Action [39].
[82] SL digital output C
See 13-52 SL Controller Action.
Output C is low on Smart Logic
Action [34]. Output C is high on
Smart Logic Action [40].
5-40 Function Relay
Array [9]
(Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB
113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6]
(MCB 105), Relay 8 [7] (MCB 105), Relay 9 [8] (MCB 105))
Option: Function:
[83] SL digital output D
See 13-52 SL Controller Action.
Output D is low on Smart Logic
Action [35]. Output D is high on
Smart Logic Action [41]
[84] SL digital output E
See 13-52 SL Controller Action.
Output E is low on Smart Logic
Action [36]. Output E is high on
Smart Logic Action [42].
[85] SL digital output F
See 13-52 SL Controller Action.
Output F is low on Smart Logic
Action [37]. Output F is high on
Smart Logic Action [43].
[120] Local ref active
Output is high when 3-13 Reference
Site = [2] Local or when
3-13 Reference Site = [0] Linked to
hand auto at the same time as the
LCP is in [Hand on] mode.
Reference site
set in
3-13 Reference
Site
Local
referen
ce
active
[120]
Remote
reference
active
[121]
Reference site:
Local
3-13 Reference
Site [2]
1 0
Reference site:
Remote
3-13 Reference
Site [1]
0 1
Reference site:
Linked to
Hand/ Auto
Hand 1 0
Hand -> off 1 0
Auto -> off 0 0
Auto 0 1
Table 6.11
[121]
Remote ref active
Output is high when 3-13 Reference
Site = Remote [1] or Linked to hand/
auto [0] while the LCP is in [Auto
on] mode. See above.
[122] No alarm Output is high when no alarm is
present.
[123] Start command
activ
Output is high when the Start
command high (i.e. via digital input,