3.12 Main Menu - Frequency Converter
Information - Group 15
Parameter group containing frequency converter
information
such as operating data, hardware configu-
ration and software versions.
3.12.1 15-0* Operating Data
15-00 Operating hours
Range: Function:
0 h* [0 - 2147483647 h] View how many hours the frequency
converter
has run. The value is saved
when the frequency converter is
turned off.
15-01 Running Hours
Range: Function:
0 h* [0 - 2147483647
h]
View how many hours the motor has
run.
Reset the counter in 15-07 Reset
Running Hours Counter. The value is
saved when the frequency converter is
turned off.
15-02 kWh Counter
Range: Function:
0 kWh* [0 - 2147483647
kWh]
Registering the power consumption
of the motor as a mean value over
one hour. Reset the counter in
15-06 Reset kWh Counter.
15-03 Power Up's
Range: Function:
0 * [0 - 2147483647 ] View the number of times the frequency
converter
has been powered up.
15-04 Over Temp's
Range: Function:
0 * [0 - 65535 ] View the number of frequency converter
temperature
faults which have occurred.
15-05 Over Volt's
Range: Function:
0 * [0 - 65535 ] View the number of frequency converter
overvoltages
which have occurred.
15-06 Reset kWh Counter
Option: Function:
[0] * Do not reset
Select [0]
Do not reset
if no reset of the kWh
counter is desired.
[1] Reset counter
Select [1] Reset
and press [OK] to reset the
kWh counter to zero (see 15-02 kWh
Counter).
NOTE
The
reset is carried out by pressing [OK].
15-07 Reset Running Hours Counter
Option: Function:
[0] * Do not reset
Select [0]
Do not reset
if no reset of the
Running Hours counter is desired.
[1] Reset counter
Select [1] Reset counter
and press [OK] to
reset the Running Hours counter
(15-01 Running Hours) and 15-08 Number of
Starts to zero (see also 15-01 Running Hours).
15-08 Number of Starts
Range: Function:
0 * [0 - 2147483647 ] This is a read out parameter only. The
counter
shows the numbers of starts
and stops caused by a normal Start/Stop
command and/or when entering/leaving
sleep mode.
NOTE
This
parameter will be reset when resetting 15-07 Reset
Running Hours Counter.
3.12.2 15-1* Data Log Settings
The Data Log enables continuous logging of up to 4 data
sources
(15-10 Logging Source) at individual rates
(15-11 Logging Interval). A trigger event (15-12 Trigger
Event) and window (15-14 Samples Before Trigger) are used
to start and stop the logging conditionally.
15-10 Logging Source
Array [4]
Option: Function:
Select which variables are to be
logged.
[0] * None
[1600] Control Word
[1601] Reference [Unit]
[1602] Reference [%]
[1603] Status Word
[1610] Power [kW]
[1611] Power [hp]
[1612] Motor Voltage
[1613] Frequency
[1614] Motor current
[1616] Torque [Nm]
[1617] Speed [RPM]
[1618] Motor Thermal
[1630] DC Link Voltage
[1632] Brake Energy /s
[1633] Brake Energy /2 min
[1634] Heatsink Temp.
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
MG16H102 - VLT
®
is a registered Danfoss trademark
99
3 3

Table of Contents

Other manuals for Danfoss VLT FC 103

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 103 and is the answer not in the manual?

Danfoss VLT FC 103 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 103
CategoryDC Drives
LanguageEnglish

Related product manuals