3.5 Main Menu - Reference/Ramps - Group
3
3.5.1 3-0* Reference Limits
3-02 Minimum Reference
Range: Function:
Size
related*
[ -999999.999 -
par.
3-03
ReferenceFeed-
backUnit]
Enter the Minimum Reference.
The Minimum Reference is the
lowest value obtainable by
summing all references. The
Minimum Reference value and
unit matches the configuration
choice made in 1-00 Configu-
ration Mode and 20-12 Reference/
Feedback Unit, respectively.
NOTE
This
parameter is used in
open loop only.
3-04 Reference Function
Option: Function:
[0] * Sum Sums both external and preset reference
sources.
[1] External/Preset Use either the preset or the external
reference
source.
Shift between external and preset via a
command on a digital input.
3-04 Reference Function
Option: Function:
[0] * Sum Sums both external and preset reference
sources.
[1] External/Preset Use either the preset or the external
reference
source.
Shift between external and preset via a
command or a digital input.
3.5.2 3-1* References
Select the preset reference(s). Select Preset ref. bit 0/1/2
[16],
[17] or [18] for the corresponding digital inputs in
parameter group 5-1*.
3-10 Preset Reference
Array [8]
Range: Function:
0 %* [-100 -
100
%]
Enter up to eight different preset references
(0-7) in this parameter, using array
programming. The preset reference is stated as
a percentage of the value Ref
MAX
(3-03 Maximum Reference, for closed loop see
20-14 Maximum Reference/Feedb.). When using
3-10 Preset Reference
Array [8]
Range: Function:
preset references, select Preset ref. bit 0/1/2
[16],
[17] or [18] for the corresponding digital
inputs in parameter group 5-1* Digital Inputs.
P3-03
P3-02
0 50 100%
P3-10
130BB036.10
Illustration 3.11
[P 5-13=Preset ref. bit 0]
Preset
[P 5-14=Preset ref. bit 1]
[P 5-15=Preset ref. bit 2]
10101010
76543210
29
12
(+24V)
11001100
32
11110000
33
130BA149.10
Illustration 3.12
3-11 Jog Speed [Hz]
Range: Function:
Size related* [ 0
- par.
4-14
Hz]
The jog speed is a fixed output
speed at which the frequency
converter is running when the jog
function is activated.
See also 3-80 Jog Ramp Time.
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
50 MG16H102 - VLT
®
is a registered Danfoss trademark
33

Table of Contents

Other manuals for Danfoss VLT FC 103

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 103 and is the answer not in the manual?

Danfoss VLT FC 103 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 103
CategoryDC Drives
LanguageEnglish

Related product manuals