3.4 Main Menu - Brakes - Group 2
3.4.1 2-0* DC-Brakes
Parameter group for configuring the DC brake and DC
hold
functions.
2-00 DC Hold/Preheat Current
Range: Function:
50 %* [ 0 -
160
%]
Enter a value for holding current as a
percentage of the rated motor current I
M,N
set
in 1-24 Motor Current. 100% DC holding current
corresponds to I
M,N
.
This parameter holds the motor (holding
torque) or pre-heats the motor.
This parameter is active if [1] DC hold/Motor
Preheat is selected in 1-80 Function at Stop.
NOTE
2-00
DC Hold/Preheat Current will not have effect when
1-10 Motor Construction = [1] PM, non salient SPM.
NOTE
The
maximum value depends on the rated motor current.
Avoid 100 % current for too long. It may damage the
motor.
2-01 DC Brake Current
Range: Function:
50
%*
[ 0 -
1000
%]
Enter a value for current as a percentage of the
rated motor current I
M,N
, see 1-24 Motor Current.
100% DC braking current corresponds to I
M,N
.
DC brake current is applied on a stop
command, when the speed is lower than the
limit set in 2-03 DC Brake Cut In Speed [RPM];
when the DC Brake Inverse function is active; or
via the serial communication port. The braking
current is active during the time period set in
2-02 DC Braking Time.
NOTE
The
maximum value depends on the rated motor current.
Avoid 100 % current for too long. It may damage the
motor.
2-02 DC Braking Time
Range: Function:
10 s* [0 - 60 s] Set the duration of the DC braking current set
in 2-01 DC Brake Current, once activated.
2-03 DC Brake Cut In Speed [RPM]
Range: Function:
Size related* [ 0 - 0
RPM]
Set
the DC brake cut-in speed for
activation of the DC braking current
2-03 DC Brake Cut In Speed [RPM]
Range: Function:
set in 2-01
DC Brake Current, upon a
stop
command.
When 1-10 Motor Construction is set to
[1] PM non salient SPM this value is
limited to 0 rpm (OFF)
NOTE
2-03
DC Brake Cut In Speed [RPM] will not have effect when
1-10 Motor Construction = [1] PM, non salient SPM.
2-04 DC Brake Cut In Speed [Hz]
Range: Function:
Size related* [ 0 - 0.0 Hz]
2-06 Parking Current
Range: Function:
50 %* [ 0
- 1000
%]
Set
current as percentage of rated motor
current, 1-24 Motor Current. Active in
connection with 1-73 Flying Start. The ing
current is active during the time period set
in 2-07 Parking Time.
NOTE
2-06
Parking Current and 2-07 Parking Time: Only active if
PM motor construction is selected in 1-10 Motor
Construction.
2-07 Parking Time
Range: Function:
3 s* [0.1 - 60 s]
Set the duration of the ing current time set in
2-06
Parking Current. Active in connection with
1-73 Flying Start.
3.4.2 2-1* Brake Energy Funct.
Parameter group for selecting dynamic braking parameters.
Only
valid for frequency converters with brake chopper.
2-10 Brake Function
Option: Function:
Available selections depend on 1-10
Motor Construction:
[0] Asynchron:
[0] off
[1] Resistor brake
[2] AS brake
[1] PM non salient:
[0] off
[1] Resistor brake
[0] * Off No brake resistor installed.
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
48 MG16H102 - VLT
®
is a registered Danfoss trademark
33

Table of Contents

Other manuals for Danfoss VLT FC 103

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 103 and is the answer not in the manual?

Danfoss VLT FC 103 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 103
CategoryDC Drives
LanguageEnglish

Related product manuals