Par. No. # Parameter description Default value 4-set-up Change
during
operation
Conver-
sion
index
Type
26-30 Terminal X42/5 Low Voltage 0.07 V All set-ups TRUE -2 Int16
26-31 Terminal X42/5 High Voltage 10 V All set-ups TRUE -2 Int16
26-34
Term. X42/5 Low Ref./Feedb.
Value 0 N/A All set-ups TRUE -3 Int32
26-35
Term. X42/5 High Ref./Feedb.
Value 100 N/A All set-ups TRUE -3 Int32
26-36
Term. X42/5 Filter Time
Constant 0.001 s All set-ups TRUE -3 Uint16
26-37 Term. X42/5 Live Zero [1] Enabled All set-ups TRUE - Uint8
26-4* Analog Out X42/7
26-40 Terminal X42/7 Output [0] No operation All set-ups TRUE - Uint8
26-41 Terminal X42/7 Min. Scale 0 % All set-ups TRUE -2 Int16
26-42 Terminal X42/7 Max. Scale 100 % All set-ups TRUE -2 Int16
26-43 Terminal X42/7 Bus Control 0 % All set-ups TRUE -2 N2
26-44 Terminal X42/7 Timeout Preset 0 % 1 set-up TRUE -2 Uint16
26-5* Analog Out X42/9
26-50 Terminal X42/9 Output [0] No operation All set-ups TRUE - Uint8
26-51 Terminal X42/9 Min. Scale 0 % All set-ups TRUE -2 Int16
26-52 Terminal X42/9 Max. Scale 100 % All set-ups TRUE -2 Int16
26-53 Terminal X42/9 Bus Control 0 % All set-ups TRUE -2 N2
26-54 Terminal X42/9 Timeout Preset 0 % 1 set-up TRUE -2 Uint16
26-6* Analog Out X42/11
26-60 Terminal X42/11 Output [0] No operation All set-ups TRUE - Uint8
26-61 Terminal X42/11 Min. Scale 0 % All set-ups TRUE -2 Int16
26-62 Terminal X42/11 Max. Scale 100 % All set-ups TRUE -2 Int16
26-63 Terminal X42/11 Bus Control 0 % All set-ups TRUE -2 N2
26-64 Terminal X42/11 Timeout Preset 0 % 1 set-up TRUE -2 Uint16
Table 4.22
4.1.22 28-** Compressor Functions
Par. No. # Parameter description Default value 4-set-up Change
during
operation
Conver-
sion index
Type
28-2* Discharge Temperature Monitor
28-20 Temperature Source [0] None All set-ups FALSE - Uint8
28-21 Temperature Unit [60] °C All set-ups FALSE - Uint8
28-24 Warning Level 130 N/A All set-ups FALSE 0 Uint16
28-25 Warning Action [1] Decrease cooling All set-ups FALSE - Uint8
28-26 Emergency Level 145 N/A All set-ups FALSE 0 Uint16
28-27 Discharge Temperature 0 DTM_ReadoutUnit All set-ups TRUE 0 Int32
28-7* Day/Night Settings
28-71 Day/Night Bus Indicator [0] Day All set-ups TRUE - Uint8
28-72 Enable Day/Night Via Bus [0] Disabled All set-ups TRUE - Uint8
28-73 Night Setback
0 ReferenceFeed-
backUnit All set-ups TRUE -3 Int32
28-74 Night Speed Drop [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
28-75 Night Speed Drop Override 0 N/A All set-ups TRUE -3 Int32
28-76 Night Speed Drop [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
28-8* P0 Optimization
Parameter Lists
VLT
®
Refrigeration Drive Programming Guide
MG16H102 - VLT
®
is a registered Danfoss trademark
187