9-28 Process Control
Option: Function:
[1]
*
Enable
cyclic
master
Enables process control via PROFIBUS master class
1 and disables process control via standard
eldbus or PROFIBUS master class 2.
9-44 Fault Message Counter
Range: Function:
0* [0 -
65535 ]
Indicates the number of fault events presently
stored in parameter 9-45 Fault Code. The buer
capacity is maximum 8 error events. The buer
and counter are set to 0 by reset or power-up.
9-45 Fault Code
Range: Function:
0* [0 - 0 ] This buer contains the alarm word for all alarms
and warnings that have occurred since last reset or
power-up. The buer capacity is maximum 8 error
events.
9-47 Fault Number
Range: Function:
0* [0 - 0 ] This buer contains the alarm word for all alarms
and warnings that have occurred since last reset or
power-up. The buer capacity is maximum 8 error
events.
9-52 Fault Situation Counter
Range: Function:
0* [0 - 1000 ] Indicates the number of fault events that have
occurred since last reset or power-up.
9-53 Probus Warning Word
Range: Function:
0* [0 -
65535 ]
This parameter shows PROFIBUS communication
warnings.
Bit Description
0 Connection with DP master is lost.
1 Not used.
2 FDL (eldbus data link layer) is not
OK.
3 Clear data command received.
4 Actual value is not updated.
5 Baud rate search.
6 PROFIBUS ASIC is not transmitting.
7 Initializing of PROFIBUS is not OK.
8 Frequency converter is tripped.
9 Internal CAN error.
10 Wrong conguration data from PLC.
11 Wrong ID sent by PLC.
12 Internal fault occurred.
13 Not congured.
14 Timeout active.
15 Warning 34 active.
Table 4.5 Bit Denition
9-63 Actual Baud Rate
Option: Function:
This parameter shows the actual
PROFIBUS baud rate. The PROFIBUS
master automatically sets the baud
rate.
[0] 9,6 kbit/s
[1] 19,2 kbit/s
[2] 93,75 kbit/s
[3] 187,5 kbit/s
[4] 500 kbit/s
[6] 1500 kbit/s
[7] 3000 kbit/s
[8] 6000 kbit/s
[9] 12000 kbit/s
[10] 31,25 kbit/s
[11] 45,45 kbit/s
[255] * No baudrate found
9-64 Device Identication
Range: Function:
0* [0 -
0 ]
NOTICE
This parameter is not visible via LCP.
The device identication parameter. The data type
is array[n] of unsigned16. The assignment of the 1st
subindexes is dened and shown in Table 4.6.
Parameter Descriptions
VLT
®
Midi Drive FC 280
78 Danfoss A/S © 12/2015 All rights reserved. MG07C102