EtherNet/IP Operation Manual
8-22
_8
Instance
Attribute
Name
Access
Rule
Data Type Values Description
Out Errors
UDINT 16#0
Number of the interface packets
sent but errors occurred
16#05
Media Counters
Get
STRUCT
of
16#0
Enthernet interface error
counter; only available for
AHRTU-ETHN-5A
Alignment Errors
UDINT 16#0
The number of times when the
length of the received packet is
not a bit integral
FCS Errors
UDINT 16#0
The number of times when the FCS
error check runs during packet
receiving period
Single Collisions
UDINT 16#0
The number of times when the
packet is sent successfully but with
one collision
Multiple Collisions
UDINT 16#0
The number of times when the
packet is sent successfully but with
multiple collisions
SQE Test Errors
UDINT 16#0
The number of times an error
message appears when SQE test
runs
Deferred
Transmissions
UDINT 16#0
The number of times when the
transmission is deferred due to
busy interface
Late Collisions
UDINT 16#0
The number of times an collision
occurs during packet sending
Excessive Collisions
UDINT 16#0
The number of times when the
packet cannot be sent due to carrier
sense and excessive collisions
occur
MAC Transmit Errors
UDINT 16#0
The number of times when the
packet cannot be sent due to MAC
layer errors
Carrier Sense Errors
UDINT 16#0
The number of times when no
response on the carrier sense or no
resent during the sending of the
packets.
Frame Too Long
UDINT 16#0
The number of times when the
lengh of the received packet
exceeds the upper limit.
MAC Receive Errors
UDINT 16#0
The number of times when an error
occurs on the packet receiving due
to MAC layer error
16#0A
Interface Label
Get
SHORT_S
TRING
NA
Define the Ethernet port name
For example: AH10EN-5A When
Ethernet port is x1, the expression
will be 02 78 31.
For port 1, the definition of the name
in string is 01 31.
Length USINT NA
The maximum length of the name is
16 characters.
Interface name
SHORT_S
TRING
NA
Use ASCII characters to name the
Ethernet port name.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AHCPU560-EN2 Series and is the answer not in the manual?

Delta AHCPU560-EN2 Series Specifications

General IconGeneral
BrandDelta
ModelAHCPU560-EN2 Series
CategoryNetwork Hardware
LanguageEnglish

Related product manuals