EasyManuals Logo
Home>Delta>Network Hardware>AS02HC-A

Delta AS02HC-A User Manual

Delta AS02HC-A
632 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #322 background imageLoading...
Page #322 background image
AS Series Module Manual
9- 32
_9
3. Click Change in the section of Module Definition under the General tab to change the data length (see the
image above). You can see the default data size as shown below. Here only shows the data exchange area
of AS00SCM. You can find more information on the data size of the right-side modules in the following steps.
4. Digital modules: the data size of every digital modules is incremented in RTU IO Owner. You can refer to
the following table for the data size of each module; the unit is INT. When converting INT value to SINT
value, the INT value needs to multiply 2 and add the sum to the value to make it a SINT value. Use
AS16AP11P-A as an example, if the INT value is 1 and to convert it to SINT value, the INT value 1
multiplies 2 is 2. Add the sum 2 to the value to make it a SINT value. The input data size is 62 (60+ (1*2)),
the output data is 42 (40+(1*2)).
Digital I/O Module
I/O Data Length (Unit: INT)
ASRTU-FEN02 → EtherNet/IP Scanner
(Input)
EtherNet/IP Scanner → ASRTU-FEN02
(Output)
AS08AM10N-A
1
0
AS08AN01T-A
0
1
AS08AN01P-A
0
1
AS08AN01R-A
0
1
AS16AM10N-A
1
0
AS16AP11T-A
1
1
AS16AP11P-A
1
1
AS16AP11R-A
1
1
AS16AN01T-A 0 1
AS16AN01P-A 0 1
AS16AN01R-A 0 1
AS32AM10N-A
2
0
AS32AN02T-A
0
2
AS64AM10N-A
4
0
AS64AN02T-A
0
4