Chapter 10 Function Cards
10-45
10.2.9.3 Specifications
System Specifications
General
Star and linear topologies are supported.
IP Settings
When installed on AS300 PLC CPU, you can use
HWCONFIG from ISPSoft for editing
Web
Functions
View device information
Account management
AS-FOPC02 firmware update
OPC-UA Specifications
OPC-UA Server
Security mode
(2) Sign
Security policy
(1) Basic128Rsa15
(2) Basic256
Authentication
(1) Anonymous
Transport protocol / encoding
UA v1.03 Nano Embedded Device Server Profile
EtherNet/IP Specifications
Adapter
CIP Network I/O
Connection
Requested Packet Interval
1 ms~1000ms
Max. data length/per
200 bytes
CIP Network
Explicit Message
Total 8 (Servers)
(for both class 3 and UCMM connection types)
UCMM
(Non-Connected Type, only
CIP Objects
Identity Object (16#01)
Message Router Object (16#02)
Assembly Object (16#04)
Connection Manager Object (16#06)
Port Object (16#F4)
TCP/IP Interface Object (16#F5)
Ethernet Link Object (16#F6)
Not supporting self-defined objects