5
VFD-B Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-39
06-01
Over-Current
Detection
Level
Current
Output Frequency
Over-Current Stall
prevention during
Acceleration,
frequency held
06 - 02
Over-current Stall Prevention during Operation
Factory Setting: 170
Settings 20 to 250% Unit: 1%

If the output current exceeds the setting specified in Pr.06-02 (the over-current stall
prevention current level during operation) when the drive is operating, the drive will
decrease its output frequency to prevent the motor stall. If the output current is lower
than the setting specified in Pr.06-02, the drive will then accelerate to catch up with the
frequency specified.
06-02
Over-Current
Detection
Level
Output Current
Output
Frequency
Over-Current Stall
Prevention during
Operation, output
frequency decrease