Figure 30: PX Gateway Card
Industrial Relay Card-MS
The MiniSlot Industrial Relay Card provides a way of connecting the 91PS/
93PS to industrial and electrical monitoring systems. It also enables a wide
range of control applications by allowing up to 250 volts and 8 Amperes
through its 5 relay connections. By connecting wires to the corresponding
places in its terminal blocks, you can choose Normally Open or Normally
Closed setup for each output.
For information on how to configure the Industrial Relay Card-MS, see
Section 6.7 Configuring relays.
Figure 31: Industrial Relay Card-MS
6.4 Intelligent Power Software
Intelligent Power Software are productivity tools for UPS power management.
These software solutions enhance the protection provided by a UPS by shutting
down applications and operating systems, triggering disaster recovery
procedures and migrating virtual machines in case of an extended power outage.
They also help in reducing downtime and increasing the reliability of the UPS by
alarming the operators of issues and monitoring vital meters. The software can
also be used to view the usage characteristics of power equipment across the
enterprise and use the data to optimize the use of the facilities.
© Eaton Corporation plc 2020. All rights reserved. Revision: 006 Document ID: P-164000493 81 (126)
Eaton 91PS/93PS UPS 8–40 kW User’s and Installation Guide

Table of Contents

Other manuals for Eaton 91PS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton 91PS and is the answer not in the manual?

Eaton 91PS Specifications

General IconGeneral
BrandEaton
Model91PS
CategoryUPS
LanguageEnglish

Related product manuals