14
Operation
OPERATIONAL MANUAL MN156001EN October 2015 www.eaton.com
Parallel Configuration
Single: Select single for a standalone unit not operating in
parallel with another active filter.
Network: Select if all units that are operating can be
networked together for parallel operation.
Legacy: Select if the unit is being added to an existing
active filter system that does not have parallel networking
capability. When selected, the total capacity of the active
filter system must be entered in the Total System Capacity
text box.
When Network Parallel is selected, two additional
parameters are displayed. These parameters are used if the
system is designed for redundant operation.
Select Parallel Rotation OFF if the system is designed with
parallel for capacity only or if the units are to equally share
the load at all times.
Select Parallel Rotation ON if the additional units should
be cycled through with the minimum number operating to
support the correction required. This is based on the Parallel
Priority Group parameter located under Unit Settings,
Basic Setup.
Set the Rotation Frequency to the time the lowest priority
group is off until the next priority group is off. With this
setting, the units that are on or off rotate based on the
total capacity required by the load to achieve set point.
Harmonic Enable (HCU2 type)
On this screen, you can select which individual harmonic
orders are compensated.
When ON, the harmonic order compensation is enabled.
Touching any harmonic order toggles it off or on.
Unit Settings
Unit settings are individual settings for the specific unit. This
section covers the parameters you can configure.