TROUBLESHOOTING & REFERENCES
I-6
ENGLISH
Topic Title
Matching Tables
ASH220NCDWA
Combinations
Total Capacity
Required
Adapter
Port B Port A
1/4" x 3/8" 1/4" x 3/8"
Two
Zone
7 7 14K -
9 7 16K -
9 9 18K -
12 7 19K -
12 9 21K -
12 12 24K -
ASH324NCDWA
Combinations
Total
Capacity
Required
Adapter
Port C Port B Port A
MS: 1/4" x 3/8"
EH: 1/4" x 1/2"
1/4" x 3/8" 1/4" x 3/8" MS EH
Two Zone
7 7 - - - 14K - E
9 7 - - - 16K - E
9 9 - - - 18K - E
12 7 - - - 19K - E
12 9 - - - 21K - E
12 12 - - - 24K - E
18 7 - - - 25K D -
18 9 - - - 27K D -
18 12 - - - 30K D -
Three
Zone
7 7 7 21K - E
9 7 7 23K - E
9 9 7 25K - E
12 7 7 26K - E
9 9 9 27K - E
12 9 7 28K - E
12 9 9 30K - E
12 12 7 31K* - E
18 7 7 32K* D -
12 12 9 33K* - E
ASH436NCDWA
Combinations
Total
Capacity
Required
Adapter
Port D Port C Port B Port A
1/4" x 1/2" 1/4" x 3/8" 1/4" x 3/8" 1/4" x 3/8" MS EH
Two
Zone
18 9 - - - - - - 27K -
18 12 - - - - - - 30K -
24 7 - - - - - - 31K
C
A
24 9 - - - - - - 33K
C
A
24 12 - - - - - - 36K
C
A
18 18 - - - - - - 36K D
18 24 - - - - - - 42K
A
B
24 24 - - - - - - 48K*
B
C
A (x2)
Three
Zone
9 9 9 - - - 27K E -
12 9 7 - - - 28K E -
12 9 9 - - - 30K E -
12 12 7 - - - 31K E -
18 7 7 - - - 32K -
12 12 9 - - - 33K E -
18 9 7 - - - 34K -
18 9 9 - - - 36K -
12 12 12 - - - 36K E -
18 12 7 - - - 37K -
24 7 7 - - - 38K
C
A
18 12 9 - - - 39K -
24 9 7 - - - 40K
C
A
24 9 9 - - - 42K
C
A
18 12 12 - - - 42K -
24 12 7 - - - 43K
C
A
24 12 9 - - - 45K
C
A
18 18 12 - - - 48K* D
24 12 12 - - - 48K*
C
A
Four
Zone
7 7 7 7 28K E
9 7 7 7 30K E
9 9 7 7 32K E
12 7 7 7 33K E
9 9 9 7 34K E
12 9 7 7 35K E
9 9 9 9 36K E
12 9 9 7 37K E
12 12 7 7 38K E
12 9 9 9 39K E
18 7 7 7 39K -
12 12 9 7 40K E
18 9 7 7 41K -
12 12 9 9 42K E
12 12 12 7 43K E
18 9 9 7 43K -
18 12 7 7 44K -
24 7 7 7 45K
C
A
12 12 12 9 45K E
24 9 7 7 47K*
C
A
12 12 12 12 48K* E
18 12 9 9 48K* -
*ALL INDOOR UNITS MUST BE FLEXFIT.
*ALL INDOOR UNITS MUST BE FLEXFIT.
Adapters
GEA Part #GEA Part #
A 1/4” to 3/8” (Liquid line for ports C & D) WJ01X23925
B 3/8” to 5/8” (Vapor line for port C) WJ01X23924
C 1/2” to 5/8” (Vapor line for port D) WJ01X23932
D 3/8” to 1/2” (Vapor line for port C) WJ01X26853
E 1/2” to 3/8” (Vapor line for port C OR D) WJ01X26854