4-28 F60 Feeder Protection System GE Multilin
4.2 FACEPLATE INTERFACE 4 HUMAN INTERFACES
4
By default, when an incorrect Command or Setting password has been entered via any external communications interface
three times within three minutes, the REMOTE ACCESS DENIED FlexLogic operand is set to “On” and the F60 does not allow
settings or command access via the any external communications interface for five minutes. The REMOTE ACCESS DENIED
FlexLogic operand is set to “Off” after five minutes for a Command password or 30 minutes for a Settings password.
These default settings can be changed in EnerVista under Settings > Product Setup > Security.