GE Multilin F60 Feeder Protection System F-9
APPENDIX F F.2 DNP POINT LISTS
F
F.2.2 BINARY AND CONTROL RELAY OUTPUT
Supported Control Relay Output Block fields: Pulse On, Pulse Off, Latch On, Latch Off, Paired Trip, Paired Close.
BINARY OUTPUT STATUS POINTS
Object Number: 10
Request Function Codes supported: 1 (read)
Default Variation reported when Variation 0 requested: 2 (Binary Output Status)
CONTROL RELAY OUTPUT BLOCKS
Object Number: 12
Request Function Codes supported: 3 (select), 4 (operate), 5 (direct operate), 6 (direct operate, noack)
Table F–3: BINARY/CONTROL OUTPUTS
POINT NAME/DESCRIPTION
0 Virtual Input 1
1 Virtual Input 2
2 Virtual Input 3
3 Virtual Input 4
4 Virtual Input 5
5 Virtual Input 6
6 Virtual Input 7
7 Virtual Input 8
8 Virtual Input 9
9 Virtual Input 10
10 Virtual Input 11
11 Virtual Input 12
12 Virtual Input 13
13 Virtual Input 14
14 Virtual Input 15
15 Virtual Input 16
16 Virtual Input 17
17 Virtual Input 18
18 Virtual Input 19
19 Virtual Input 20
20 Virtual Input 21
21 Virtual Input 22
22 Virtual Input 23
23 Virtual Input 24
24 Virtual Input 25
25 Virtual Input 26
26 Virtual Input 27
27 Virtual Input 28
28 Virtual Input 29
29 Virtual Input 30
30 Virtual Input 31
31 Virtual Input 32
32 Virtual Input 33
33 Virtual Input 34
34 Virtual Input 35
35 Virtual Input 36
36 Virtual Input 37
37 Virtual Input 38
38 Virtual Input 39
39 Virtual Input 40
40 Virtual Input 41
41 Virtual Input 42
42 Virtual Input 43
43 Virtual Input 44
44 Virtual Input 45
45 Virtual Input 46
46 Virtual Input 47
47 Virtual Input 48
48 Virtual Input 49
49 Virtual Input 50
50 Virtual Input 51
51 Virtual Input 52
52 Virtual Input 53
53 Virtual Input 54
54 Virtual Input 55
55 Virtual Input 56
56 Virtual Input 57
57 Virtual Input 58
58 Virtual Input 59
59 Virtual Input 60
60 Virtual Input 61
61 Virtual Input 62
62 Virtual Input 63
63 Virtual Input 64
Table F–3: BINARY/CONTROL OUTPUTS
POINT NAME/DESCRIPTION