C-24 F60 Feeder Protection System GE Multilin
C.6 ACSI CONFORMANCE APPENDIX C
C
c2: shall be "M" if support for LOGICAL-NODE model has been declared
c3: shall be "M" if support for DATA model has been declared
c4: shall be "M" if support for DATA-SET, Substitution, Report, Log Control, or Time models has been declared
c5: shall be "M" if support for Report, GSE, or SMV models has been declared
M: Mandatory
C.6.3 ACSI SERVICES CONFORMANCE STATEMENT
In the table below, the acronym AA refers to Application Associations (TP: Two Party / MC: Multicast). The c6 to c10 entries
are defined in the notes following the table.
M8-4 data-set-name
M8-5 data-reference
M8-6 BufTm
M8-7 IntgPd
M8-8 GI
Logging O
M9 Log control O
M9-1 IntgPd
M10 Log O
M11 Control M Yes
IF GSE (B31/32) IS SUPPORTED
GOOSE O Yes
M12-1 entryID
M12-2 DataReflnc
M13 GSSE O Yes
IF SVC (B41/B42) IS SUPPORTED
M14 Multicast SVC O
M15 Unicast SVC O
M16 Time M Yes
M17 File transfer O Yes
SERVICES AA: TP/MC SERVER/
PUBLISHER
UR FAMILY
SERVER (CLAUSE 7)
S1 ServerDirectory TP M Yes
APPLICATION ASSOCIATION (CLAUSE 8)
S2 Associate TP M Yes
S3 Abort TP M Yes
S4 Release TP M Yes
LOGICAL DEVICE (CLAUSE 9)
S5 LogicalDeviceDirectory TP M Yes
LOGICAL NODE (CLAUSE 10)
S6 LogicalNodeDirectory TP M Yes
S7 GetAllDataValues TP M Yes
DATA (CLAUSE 11)
S8 GetDataValues TP M Yes
S9 SetDataValues TP O Yes
S10 GetDataDirectory TP M Yes
S11 GetDataDefinition TP M Yes
SERVICES SERVER/
PUBLISHER
UR-FAMILY
NOTE