G-2 F60 Feeder Protection System GE Multilin
G.1 RADIUS SERVER CONFIGURATION APPENDIX G
G
<Path_to_Radius>/start_radiusd_debug.bat
8. Set up the RADIUS parameters on the UR as follows.
If logging in, select Device for the Authentication Type, and use Administrator for the User Name. The default pass-
word is "ChangeMe1#".
Access Settings > Product Setup > Security. Configure the IP address and ports for the RADIUS server. Leave the
GE vendor ID field at the default of 2910. Update the RADIUS shared secret as specified in the clients.conf file.
9. Verify operation. Log in to the UR software as follows. In the login window, select Server as the Authentication Type,
enter the user name entered (for example user name Tester and password "testpw"). Check that the RADIUS server
log file shows the access with an "Access-Accept" entry.
Recall that If you tried another third-party tool and it did not work, you can use the FreeRADIUS software from freera-
dius.net.