62 VDL200 • Quick installation guide - Specifications and connection
A.2.2 Phasing
In order for the VDL200 Brushless regulation algorithm to function correctly, it is necessary to know the position of
the rotor with respect to the stator power phases. Therefore the 0° position provided by the absolute encoder must
be known with respect to the position of a motor pole and the encoder count direction must match the motor power
phases.
This is called phasing. Phasing can be performed manually, directly by means of the mechanical encoder assembly
position on the motor shaft and on the phases, or using the automatic procedures available in the drive.
Phasing must always be repeated whenever:
- the encoder assembly position is changed
- the phase sequence of the motor power supply connection is changed
- the encoder incremental signal connection is changed
- the encoder absolute signal connection is changed
- the value of the PAR 2008 Pole pairs parameter is changed
- the value of the PAR 2100 Encoder pulses parameter is changed
- the drive is replaced (alternatively, download parameters taken from previous drive)
󰀨󰀨
PAR 2190 Autophase rotation -> rotation phasing:
this procedure must be performed with the motor free to turn and with no load applied.
PAR 2192 Autophase still -> static phasing:
this procedure must be performed with the motor still and brake applied.
Rotation phasing

encoder phasing, cross-check the available encoder and motor data and, if the encoder count direction does not match
the phase sequence of the motor power supply, correct it by automatically modifying PAR 2130 Encoder direction.
Note! In the case described above, a positive speed reference could generate a rotation in reverse with respect to that defined as positive for the encoder (usually
clockwise), while still ensuring good motor control.

power phases and repeating the rotation phasing procedure.
󰀨
been detected that cannot be corrected by the drive, one of the codes listed in Autotune (phasing), 
Messages, is shown.
Possible faults:
- faults in electric signals not detected with a "Speed fbk loss [22]" alarm
- error in the PAR 2008 Pole pairs parameter setting
- error in the PAR 2100 Encoder pulses parameter setting
Static phasing
Using this method, in which the motor cannot move, the encoder and motor data cannot be cross-checked to verify the
matching of parameters or count direction.
This condition must therefore be checked before launching the procedure.

Table of Contents

Other manuals for gefran VDL200 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran VDL200 Series and is the answer not in the manual?

gefran VDL200 Series Specifications

General IconGeneral
Brandgefran
ModelVDL200 Series
CategoryDC Drives
LanguageEnglish

Related product manuals