GMV5 Home DC Inverter Multi VRF Units
287
3.4-7The
outdoor
ambient
temperat
ure in the
heating
mode is
lower
than -7C.
Measure
the
outdoor
ambient
temperat
ure.
It is a
normal
phenomen
on.
4.Poor
airflow
distributi
on
design
4.1The
air intake
and
return
inlet of
the ODU
are too
close to
each
other,
affecting
the heat
exchange
performa
nce of the
unit.
Check
the
distance.
Re-design
the airflow
distributio
n.
4.2The
air intake
and
return
inlet of
the IDU
are too
close to
each
other,
causing
poor heat
exchange
of the
unit.
Check
the
distance.
Re-design
the airflow
distributio
n.
7.Not
enough
refrigera
nt
Other
reasons
Incorrect
quantity
of
refrigeran
t is
injected.
Check the
necessary
amount of
refrigerant
and inject
refrigerant
slowly via
the stop
valve of
the
low-press
ure air
pipe.
4.2Flowchart analysis
4.2.1 High exhaust temperature protection (E4)
When the system appears high exhaust temperature protection for compressor, the IDU will
display high exhaust temperature fault E4, while the IDU will display the specific faulty compressor.
For example, when high exhaust temperature protection is enabled on compressor 2# of module
3# of the ODU, IDUs will display E4 and the module will display E6, indicating that high exhaust
temperature protection is enabled on compressor 2#.