GMV5 Home DC Inverter Multi VRF Units
321
7. Check and install
the front panels.
●Check the parts and connecting
wires;
●If no problem is found, hook the
front panels and tighten the
screws.
Assembly and disassembly of gas liquid separator
Precondition: No refrigerant exists in the pipeline system and the power supply has been disconnected.
1. Loosen the hooks
at the bottom of the
electric box and the
screws.
●Remove the left and right front
panels and set them aside;
●Loosen the hooks at the bottom
of the electric box;
● Use a screwdriver to unscrew
the electric box.
2. Remove the
electric box.
●Disconnect internal and external
connecting wires of the electric
box.
●Protect the internal parts during
the disassembly.
3. Disassemble the
gas liquid separator.
●Heat up the two nozzles of
connecting pipes of gas liquid
separator with acetylene welding
and then remove the pipes.
Note: Prevent nearby parts from
being burnt during welding.