Hitachi Advanced Server HA820 G2 User Guide 186
•
The branch circuit overcurrent protection must be rated 27 A.
CAUTION:
This equipment is designed to permit the connection of the earthed
conductor of the DC supply circuit to the earthing conductor at the equipment.
If this connection is made, all of the following must be met:
•
This equipment must be connected directly to the DC supply system earthing electrode
conductor or to a bonding jumper from an earthing terminal bar or bus to which the DC
supply system earthing electrode conductor is connected.
•
This equipment must be located in the same immediate area (such as adjacent cabinets)
as any other equipment that has a connection between the earthed conductor of the same
DC supply circuit and the earthing conductor, and also the point of earthing of the DC
system. The DC system must be earthed elsewhere.
•
The DC supply source is to be located within the same premises as the equipment.
•
Switching or disconnecting devices must not be in the earthed circuit conductor between
the DC source and the point of connection of the earthing electrode conductor.
1600 W Flex Slot Platinum Hot-plug Low Halogen Power Supply
Specification Value
Input requirements —
Rated input voltage 200 VAC to 240 VAC 240 VDC for China only
Rated input frequency 50 Hz to 60 Hz
Rated input current 8.7 A at 200 VAC
7.5 A at 230 VAC
Maximum rated input power 1734 W at 200 VAC 1727 W at 230 VAC
BTUs per hour 5918 at 200 VAC
5891 at 230 VAC
Power supply output —
Rated steady-state power 1600 W at 200 VAC to 240 VAC input 1600 W
at 240 VDC input
Maximum peak power 2200 W for 1 ms (turbo mode) at 200 VAC to
240 VAC input