32
PMEN0643 rev.0 - 04/2023
6
ELECTRICAL CONNECTION
ELECTRICAL AND CONTROL SETTINGS
6.2 Electrical connecon
! CAUTION
• Check to ensure that the eld supplied electrical components (mains power switches, circuit
breakers, wires, connectors and wire terminals) have been properly selected according to the
electrical data indicated on this chapter and they comply with naonal and local codes. If it is
necessary, contact with your local authority in regards to standards, rules, regulaons, etc.
• Use a dedicated power circuit for the indoor unit. Do not use a power circuit shared with the
outdoor unit or any other appliance.
6.2.1 Wiring size
Use wires which are not lighter than the polychloroprene sheathed exible cord (code designaon
60245 IEC 57).
Model Power supply Operaon mode
Maximum
current
(A)
Power supply
cables
Transming
cables
Actuator
cables
EN60335‑1 EN60335‑1 EN60335‑1
RWM‑(1.5‑3.0)R2E
~ 230V 50Hz
Without electric heaters 0.6 2 x 0.75 mm
2
+ GND
2 x
0.75 mm
2
(Shielded
cable)
2 x
0.75 mm
2
+ GND
With electric heater
13.7 2 x 2.5 mm
2
+ GND
With DHW tank heater 12.6 2 x 2.5 mm
2
+ GND
With electric and DHW tank
heaters
25.6 2 x 6.0 mm
2
+ GND
3N~ 400V
50Hz
Without electric heaters 0.6 4 x 0.75 mm
2
+ GND
With electric heater 5 4 x 2.5 mm
2
+ GND
With DHW tank heater 12.6 4 x 2.5 mm
2
+ GND
With electric and DHW tank
heaters
16.9 4 x 6.0 mm
2
+ GND
NOTE
The data corresponding to DHW tank heater is calculated in combinaon with the domesc hot
water tank accessory “DHWT‑(200/300)S‑3.0H2E”.