Extinguishing Control Computer 8010 - Series 2
FB 798352 / 11.07 65
Technical zone no.10 to no.13 (yellow LED)
Off
Î
Normal operation, technical zone is alarm-ready
Lights up yellow
Î
1) Triggers the technical zone 10 to 13
Î
2) Switch-off. The technical zone was switched off. The yellow LED >Switch off<
also lights up
Flashes yellow
Î
Trouble
Twinkle yellow
Î
Input check- the zone number was entered via the control panel keypad
12.1.2 Status display of the outputs
Status display of the
outputs is switched on
12345678
9 10111213
Detector zone
Fire/Switch off/Trouble
In operation
Switching off
Test operation
Extra releasing 1
Outputs
Alarm
Emergency release
Extinguishing system
activated
Extinguishing system
enabled
Fig. 3: Outputs displays
Outputs no.1 to no.13 (yellow LED)
Off
Î
Normal operation, the output is in the resting state
Flashes
Î
Output failure
On
Î
Output deactivated
Twinkle
Î
Input check -the output number was entered via the control panel keypad
Disconnected or zones in trouble will not signal an alarm in case of an event!

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Esser 2 Series and is the answer not in the manual?

Honeywell Esser 2 Series Specifications

General IconGeneral
BrandHoneywell
ModelEsser 2 Series
CategoryControl Unit
LanguageEnglish

Related product manuals