Extinguishing Control Computer 8010 - Series 2
FB 798352 / 11.07 95
F5, F6, F8, F9,
F11, F12, F13, F16
Fuses - low-voltage relays no. 1 to 8
Relay 1: F16, T2 A / 250 V
Relay 2: F13, T2 A / 250 V
Relay 3: F12, T2 A / 250 V
Relay 4: F11, T2 A / 250 V
Relay 5: F9, T2 A / 250 V
Relay 6: F8, T2 A / 250 V
Relay 7: F6, T2 A / 250 V
Relay 8: F5, T2 A / 250 V
F2, F3, F4
Fuses - low-voltage relays No. 9, 10 and 11
Relay 9: F2, T2 A / 250 V
Relay 10: F3, T2 A / 250 V
Relay 11: F4, T2 A / 250 V
F1, F7
Fuses - Mains voltage relays
Relay 12: F1, T 3,15 A / 250 V
Relay 13: F7, T 3,15 A / 250 V
F10
Fuses of the supply voltage for external units, UBext, T 3,15 A / 250 V
F14, F15
Fuses of the emergency power supply (rechargeable battery)
Battery 1: F14, T 3,15 A / 250 V
Battery 2: F15, T 3,15 A / 250 V
J1 to J4, J6,
J8 to J18
Jumpers to program the operating mode for relay no. 1 to 8,
(monitoring or dry contact).
Factory setting Î monitoring
J5
Jumper to set the CPU-failure-mode function for relay 11
Emergency operation - fault
Inactive Î deactivated (factory setting)
Active Î activated
J7
Jumper to set the CPU-failure-mode function for relay 10
>Emergency operation - fire <
Inactive Î deactivated (factory setting)
Active Î activated
Poti
Potentiometer for adjusting the battery charging voltage 27.5 V DC (@ 25°C)
Relay 1 to 8
Low-voltage relays, monitored or dry contact
Relay. 9 to Rel. 11
Low-voltage relays, dry contact
contact rating
30 V DC / 2 A
Relay 12 + 13
Mains voltage relays, dry contact
contact rating
230 V AC / 2 A
X47
Terminal for the ribbon cable to the zone board
X57
Plug for PE connection to the housings rear wall
X11 / UB
EXT
Terminals for the Supply voltage for external units +24 V DC / GND

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Esser 2 Series and is the answer not in the manual?

Honeywell Esser 2 Series Specifications

General IconGeneral
BrandHoneywell
ModelEsser 2 Series
CategoryControl Unit
LanguageEnglish

Related product manuals