ID2000 Series Operating Manual
Operator Actions at Panel
10997-434-000-4, Issue 4
May 2010
4.3 Accept
The ACCEPT pushbutton has the following functions in
FIRE or FAULT condition:
Note: If the panel is in DAY mode (Section 4.12 or may
be configured with time-of-day), and ACCEPT is
operated during the first investigation time (while
the DAY MODE LED is flashing), the delay time
before the remote fire output is operated is
extended.
a. The internal buzzer is silenced as described for the
MUTE BUZZER pushbutton (see Section 4.2).
Flashing lamps change to steady.
b. A horizontally-scrollable text display gives further
information about the events which have occurred. In
particular, those FAULTs which are identified at Top
Level display only as a SYSTEM FAULT with a
number, are now described in full. The first event is
shown first. Use and to scroll through the text
display.
c. If more than one event is outstanding since the last
time that the RESET pushbutton was pressed, you
may step through the events by:
i Operating the up or down arrow keys (to go
backwards or forwards in time respectively).
‘MORE’ appears on the text display to indicate
further events.
ii Press
to revert to the top-level display (if no
key is pressed within 20 seconds the system
reverts to the Top Level display automatically).
d. The ACCEPT pushbutton may be pressed at any time
in order to review these events, not only when the
internal buzzers are operating.
e. If extendable sounder delays are configured, the
ACCEPT pushbutton extends the delay.
f. As a special case, if the fault LOSS OF PART LOOP
has occurred and has not been cleared, a detailed
report can be obtained on all the devices recorded as
missing:
i Press
at any time, and the system, if
appropriate, displays the following:
ii If
is pressed again, all the individual devices
involved are reported with separate NO REPLY/
MISSING messages (this will cause normal
FAULT action to take place).
iii The devices can then be reviewed by pressing
ACCEPT again and stepping up and down
through the events.
Log each missing device individually?
(
!!
!!
!/X)?
DOWN = BACKWARDS IN TIME
UP = FORWARDS IN TIME

Other manuals for Honeywell NOTIFIER ID2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER ID2000 Series and is the answer not in the manual?

Honeywell NOTIFIER ID2000 Series Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER ID2000 Series
CategoryControl Panel
LanguageEnglish

Related product manuals