EasyManuals Logo
Home>Honeywell>Transmitter>XNX-UTAI Series

Honeywell XNX-UTAI Series User Manual

Honeywell XNX-UTAI Series
207 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #71 background imageLoading...
Page #71 background image
XNX Universal Transmitter
Installation and Operation
69
Changing the Gas or Units Name
If “Other mA Sensor” has been selected as the sensor type, the
existing gas and units can be renamed.
From the Gas Selection
menu, select
to open the Gas Name menu. Select
again to
open the Gas Name editing display. The rst letter of the current
selection will be highlighted (Figure 80).
Figure 80. Gas Name screen / Gas Name editing screen
Use the switches to cycle through the 76 options (26 capital
letters, 26 lower case letters, 10 numbers, 13 typographic
characters, and a space). When the rst character of the new
gas name has been reached, select
to advance to the second
character. Repeat this procedure with each character until
the new gas name is displayed. In this example, “mA Sensor”
has been changed to “Flow Sensor” (Figure 83). The name
can be up to 15 characters long. Select
to return to the Gas
Name screen. The new name will be displayed in reverse (light
characters on a dark background). Select the
switch twice to
display the Accept Settings screen. Select
to accept the new
gas name. A “Settings Accepted” screen will be displayed briey,
followed by the Gas Selection menu.
Figure 81. Accepting the New Gas Name screens
Follow the same procedure to rename the units (“%” in the
illustrations). The units name can be up to 5 characters long.
Gas Selections and Alarm Limits Based on mV Sensor
Type
These tables show the tranmsitter’s programmable alarm limits.
Note: -2 Gas Selection %LEL values are per IEC 60079-20-1:2010
Alarm Limits (% Vol)
MPD-IC1 (5%V)
Carbon Dioxide
Lower
0.5
Upper
5.0
MPD-IV1 (5%V/V, 100%LEL)
Methane Methane-1 Methane-2
Lower Alarm Limit
0.5% Vol 10% LEL 10% LEL
Upper Alarm Limit 5.0% Vol 60% LEL 60% LEL
% Volume Reference
n/a 5.0 4.4
MPD-IF1 (100%LEL)
Propane-1 Propane-2
Lower Alarm Limit
(% LEL)
10 10
Upper Alarm Limit
(% LEL)
60 60
% Volume Reference
2.0 1.7

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell XNX-UTAI Series and is the answer not in the manual?

Honeywell XNX-UTAI Series Specifications

General IconGeneral
BrandHoneywell
ModelXNX-UTAI Series
CategoryTransmitter
LanguageEnglish

Related product manuals