XNX Universal Transmitter
Installation and Operation
88
Figure 146. Inhibit menu
Use the switches to inhibit alarms by selecting Inhibit On
with the
✓
. The conrmation screen appears.
Figure 147. Conrm Inhibit On screen
Select
✓
to place the transmitter alarms into inhibit mode. Select
✖
will cancel the choice and leave the alarms in normal operating
mode.
Figure 148. Conrm Inhibit Off screen
To return from Inhibit mode to to the normal monitoring mode,
select Inhibit Off with the
✓
. A conrmation screen appears.
Select
✓
to remove the transmitter from Inhibit mode. Select ‘X”
to cancel the choice and leave the alarms in Inhibit mode.
Figure 149. Inhibit Status screen
When the transmitter is in Inhibit mode, the General Status
display will display the inhibit icon
.
Force mA Output
Caution: The mA output set in this menu will revert to the normal operating values
when exiting the Test Menu. For more information on setting the mA output levels for
normal operation, see mA Levels.
!
Force mA Output allows peripheral devices driven by mA output
from the transmitter to be tested. Based on the mA output
values set in the mA Levels option (see mA Levels), the operator
chooses the mA level to output to the device.
Figure 150. Force mA Output screen
The New mA Output screen shows the current mA output in the
left column. The output can be controlled by changing the value
in the column on the right.