Declared Noise Emissions in Accordance with ISO 9296
(1,2,3)
Product
Description
Declared A-
Weighted Sound
Power Level, L
WAd
(B)
Declared A-
Weighted Sound
Pressure Level,
L
pAm
(dB)
Operating Idling Operating Idling
5147-106 (at 23
degrees C)
8.1
(5)
7.9
(5)
66
(4)
63
(4)
5147-106 (at 27
degrees C)
8.8
(5)
8.3
(5)
72
(4)
67
(4)
5147-106
Maximum ambient
temperature
Maximum work
load (operation)
9.9
(5)
9.9
(5)
83
(4)
83
(4)
5147-106
Acoustical Doors
FC EC07 = back
9.4
(4)(5)
9.4
(4)(5)
78
(4)
78
(4)
Notes:
1. Declared level L
WAd
is the upper-limit A-weighted sound power level; Declared level L
pAm
is the mean
A-weighted sound pressure level measured at the 1-meter bystander positions.
2. All measurements made in conformance with ISO 7779 and declared in conformance with ISO 9296.
3. B, dB, abbreviations for bels and decibels, respectively. 1 B = 10 dB.
4. Estimate
5. Notice: Government regulations (such as those prescribed by OSHA or European Community
Directives) may govern noise level exposure in the workplace and may apply to you and your server
installation. This IBM system is available with an optional acoustical door feature that can help
reduce the noise emitted from this system. The actual sound pressure levels in your installation
depend upon a variety of factors, including the number of racks in the installation; the size, materials,
and conguration of the room where you designate the racks to be installed; the noise levels from
other equipment; the room ambient temperature, and employees' location in relation to the
equipment. Further, compliance with such government regulations also depends upon a variety of
additional factors, including the duration of employees' exposure and whether employees wear
hearing protection. IBM recommends that you consult with qualied experts in this eld to
determine whether you are in compliance with the applicable regulations.
Environmental requirements
Table 15. Ambient temperature and humidity
Specication Temperature range Relative humidity
Operating 5ºC to 35ºC (41ºF to 95ºF, de-
rated by 1ºC per 300m above
900m) (ASHRAE A2 2015
thermal guidelines)
-12ºC DP/10 to 80% (Max) (Non-
condensing)
84 IBM ESS expansion: Hardware Installation and Maintenance Guide - Model 106