5 Parameter Table
- 27 -
5 Parameter Table
5�1 General Parameters
Group F0: Standard Parameters
Para� No� Para� Name Setting Range Unit Default Commission
F0-01 Motor 1 control mode 0: Sensorless vector control (SVC)
2: Voltage/Frequency control (V/F)
N�A� 2
F0-02 Command source
selection
0 to 2 N�A� 0
F0-03 Main frequency source
X selection
0 to 9 N�A� 0
F0-04 Auxiliary frequency
source Y selection
The same as F0-03 (Main frequency source
X selection)
N�A� 0
F0-05 Range base of auxiliary
frequency Y for X and Y
operation superposition
0: Relative to max� frequency
1: Relative to main frequency X
N�A� 0
F0-06 Range of auxiliary
frequency Y for X and Y
operation superposition
0 to150 % 100
F0-07 Frequency source
superposition selection
00 to 34 N�A� 00
F0-08 Preset frequency 0�00 to max frequency (F0-10) N�A� 50�00
F0-09 Rotation direction 0: Same direction
1: Reverse direction
N�A� 0
F0-10 Max� frequency 50�00 to 600�00 Hz 50�00
F0-11 Source of frequency
upper limit
0 to 5 N�A� 0
F0-12 Frequency upper limit Frequency lower limit (F0-14) to max�
frequency (F0-10)
Hz 50�00
F0-13 Frequency upper limit
offset
0�00 to max frequency (F0-10) Hz 0�00
F0-14 Frequency lower limit 0�00 to frequency upper limit (F0-12) Hz 0�00
F0-15 Carrier frequency 0�8 to 16�0 kHz Model
dependent
F0-16 Carrier frequency
adjustment with
temperature
0: No
1: Yes
N�A� 1
F0-17 Acceleration time 1 0�00 to 650�00 (if F0-19 = 2)
0�0 to 6500�0 (if F0-19 = 1)
0 to 65000 (if F0-19 = 0)
s Model
dependent
F0-18 Deceleration time 1 0�00 to 650�00 (if F0-19 = 2)
0�0 to 6500�0 (if F0-19 = 1)
0 to 65000 (if F0-19 = 0)
s Model
dependent
F0-19 Acceleration/
Deceleration time unit
0: 1
1: 0�1
2: 0�01
s 1
F0-21 Frequency offset of
auxiliary frequency
source for X and Y
operation superposition
0�00 to max frequency (F0-10) Hz 0�00
F0-22 Reserved - - -

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Inovance MD310 T1.5B and is the answer not in the manual?

Inovance MD310 T1.5B Specifications

General IconGeneral
Power1.5 kW
Storage Temperature-20°C to +60°C
Power Supply Voltage380-480 VAC
Control ModeV/F control, Sensorless vector control
Protection FeaturesOver-voltage, Under-voltage, Over-current, Overload, Short-circuit
Communication InterfaceRS485, Modbus RTU
Operating Temperature-10°C to +40°C
Humidity5% to 95% (non-condensing)
AltitudeUp to 1000 m