5 Parameter Table
- 32 -
Para� No� Para� Name Setting Range Unit Default Commission
F4-34 Setting for AI less than
minimum input
000 to 111 N�A� 000
F4-35 DI1 delay time 0�0 to 3600�0 s 0�0
F4-36 DI2 delay time 0�0 to 3600�0 s 0�0
F4-37 DI3 delay time 0�0 to 3600�0 s 0�0
F4-38 DI active mode selection 1 00000 to 11111 N�A� 00000
F4-39 DI active mode selection 2 00000 to 11111 N�A� 00000
■
Group F5: Output Terminals
Para� No� Para� Name Setting Range Unit Default Commission
F5-00 FM terminal output mode 0 to 1 N�A� 0
F5-01 FMR function (open-
collector output terminal)
selection
0 to 41 N�A� 0
F5-02 Relay function (T/A-T/B-T/
C) selection
0 to 41 N�A� 2
F5-03 Extension card relay
function (P/A-P/B-P/C)
selection
0 to 41 N�A� 0
F5-04 DO1 function selection
(open-collector output
terminal)
0 to 41 N�A� 1
F5-05 Extension card DO2
function selection
0 to 41 N�A� 4
F5-06 FMP function selection 0 to 16 N�A� 0
F5-07 AO1 function selection 0 to 16 N�A� 0
F5-08 AO2 function selection 0 to 16 N�A� 1
F5-09 Max� FMP output frequency 0�01 to 50�00 kHz 50�00
F5-10 AO1 zero offset coefcient -100�0 to 100�0 % 0�0
F5-11 AO1 gain -10�00 to10�00 N�A� 1�00
F5-12 AO2 zero offset coefcient -100�0 to +100�0 % 0�00
F5-13 AO2 gain -10�00 to +10�00 N�A� 1�00
F5-17 FMR output delay time 0�0 to 3600�0 s 0�0
F5-18 Relay 1 output delay time 0�0 to 3600�0 s 0�0
F5-19 Relay 2 output delay time 0�0 to 3600�0 s 0�0
F5-20 DO1 output delay time 0�0 to 3600�0 s 0�0
F5-21 DO2 output delay time 0�0 to 3600�0 s 0�0
F5-22 DO active mode selection 00000 to 11111 N�A� 00000