8 Change of the Safety Module
Danger
Electric Shock
Before working with the unit disconnect it from mains. Check the iso-
lation from supply by measurements in the unit. Await min. 15 minutes
until the capacities of the DC link are discharged.
A change of the safety module is displayed by the control in the COMBIVIS with status 61 „ERROR
safetymod.changed“.Theusermustconrmthechangebywritingofparameterde.38"serial
number safety module" with the entered value. Only then the error can be reset.
The parameters for acknowledge the safety module change are password protected. The work can
becarriedoutonlybyqualiedpersons.
CAUTION
Working after the change
Thechangemaybedoneonlybyqualiedpersons.Checkthesafety
functions and error responses and generate an acceptance report after
the change.