Section 7 Decision-Makerr 6000 ControllerTP-6356 4/12
7.3 Request and Error Messages
Note: When EEPROM errors occur or initializing the
EEPROM is required, contact an authorized
distributor/dealer.
Request and Status Messages
Display messages require the user to enter additional
data, confirm the previous entry or require time to
process as described below.
Entry Accepted appears for several seconds after
pressing the Enter key during the programming mode.
The display then shows the new data.
Initialize EEPROM? Prompt to confirm EEPROM
initialization.
Reset Complete indicates the user has successfully:
D Reset the maintenance records,
D Restored the AC analog inputs to the default settings,
or
D Restored voltage regulator settings to the defaults.
Right Arrow → directs the user to the next menu. The
menus loop; press the right arrow key to move to the
next menu.
Setup Complete indicates the completion of the analog
input setup.
Setup Locked appears when user attempts to change a
value or perform a function available only when the
system is unlocked.
Setup Unlocked appears when user has unlocked the
system for maintenance or troubleshooting.
(Question) ? asked by the control firmware; answer the
question by pressing the yes/no, numeric digit, or
am/pm key.
Wait for System Reset (6 Sec) appears while the
EEPROM initializes.
Error Messages
When an error message appears, the entered
information is not within the allowable parameters set by
the control firmware or is not permitted as described
below. In cases where the data was outside the
parameters, press the Reset Menu key and enter the
corrected information.
Access Denied appears when the user attempts to:
D Enter data prohibited by the master switch position,
D Enter data prohibited by the generator set state, or
D Enable the LDD (load disturbance detection).
Access Denied Idle Mode Active appears when the
user attempts to modify the voltage regulator setup
while the idle mode is active.
Alarm Active appears when the user attempts to modify
an analog or a digital input that is active. See Menu
9—Input Setup.
Cannot Change Preset appears when the user
attempts to change the factory preset analog input,
digital input, or input parameter.
EEPROM Write Error appears when a component
failure occurs. Contact an authorized distributor/dealer.
Entry Unacceptable appears when the user attempts
an invalid input to the voltage regulator setup.
Some alternators are intended to operate within a
specific, limited range of conditions (voltage, frequency,
and phase or connection). The following error messages
can appear when attempts are made to enter system
values that do not match acceptable conditions for the
particular alternator.
D Fixed Frequency when entry is beyond the range of
limited entries for the respective alternator. Occurs
when the alternator is not rated for the value entered.
Updated parameter files may be available by
contacting an authorized service dealer/distributor.
D Fixed Phase when entry is beyond the range of
limited entries for the respective alternator. Occurs
when the alternator is not rated for the value entered.
Updated parameter files may be available by
contacting an authorized service dealer/distributor.
D Fixed Voltage when entry is beyond the range of
limited entries for the respective alternator. Occurs
when the alternator is not rated for the value entered.
Updated parameter files may be available by
contacting an authorized service dealer/distributor.
Func (Function) Used by (RDO) XX Reassign?
appears when the user attempts to assign an RDO to a
function already assigned.
GenSet S/N Warning appears when a controller
replacement is being done and Menu 20 Factory Setup
needs data entry. Refer to Section 7.6 Decision-Makerr
6000 Controller Replacement.
Internal Error appears when controller logic detects a
functional sequence error.

Table of Contents

Other manuals for Kohler Decision-Maker 550

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler Decision-Maker 550 and is the answer not in the manual?

Kohler Decision-Maker 550 Specifications

General IconGeneral
BrandKohler
ModelDecision-Maker 550
CategoryPortable Generator
LanguageEnglish

Related product manuals