242
8 CO/O
2
Control
Resetting Faults
Faults are reset in different ways:
Resetting temporary faults (ot):
The fault is displayed for as long as it is present. Once the cause of the fault is eliminated, the
fault is deleted, and the fault status signal no longer displayed.
Resetting permanent faults (od) at startup of the burner:
Each time the burner starts up, a fault is automatically reset, even if the cause of the fault has
not yet been eliminated. If the cause has not yet been eliminated, the fault will re-occur.
Resetting permanent faults (od) manually:
You can also reset permanent faults (od) manually after eliminating the cause.
UI400: Open the fault status signal using the arrow keys (see chapter History) and acknowl-
edge the fault with .
CMS Remote Software: Use the RESET buttons in the header bar of the CMS Remote Soft-
ware.
Chart/Trace (Recording Tool)
The recording tool can be used to record and store various values for evaluation and docu-
mentation purposes.
Fig. 8-34 Chart/Trace menu
Fig. 8-35 Chart view