Basic units in the power range 45 ... 55 kW
Power connections
6
Basic unit wiring
6.7
6.7.2
L
6.7-4
EDS82EV903-1.0-11/2002
6.7.2 Power connections
Mains connection 400/500 V
0
1
L1
L2
L3
N
PE
+UG
-UG
Z1
PE
L1
L2
L3
3/PE AC 400V
T2
T1
L2
L3
L1
2
3
3
3
3
4
4
L1
L2 L3
+UG
-UG
PE
l
3/PE AC 400V
PE
L1, L2, L3
+UG, -UG
PE
15 Nm
132 lb-in
M8
PE L1’ L2’ L3’
Gerät / Load
Z1
L1
L2
L3
+UG
-UG
PE
l
PE
L1, L2, L3
+UG, -UG
PE
15 Nm
132 lb-in
M8
T1
T2
2,5 Nm
22,1 lb-in
L1
L2
L3
+UG
-UG
3/PE AC 400V
PE
l
L1 L2 L3
+UG, -UG
PE
M8
15 Nm
132 lb-in
PE
E82EV453K4:
2-6 Nm (17,7-53,1 lb-in)
E82EV553K4:
6-12 Nm (53,1-106,2 lb-in)
L1, L2,
L3
ϑ>
8200vec289
Fig. 6.7-2 Mains connection 45 ... 55 kW
0
Connection with mains choke
1
Connection with footprint mains filter
2
Connection with built-on mains filter
3
Connection brake chopper ( ^ Operating Instructions for the brake chopper )
4
Connection of temperature monitoring for mains filter (thermal contact)
Z1 Mains choke/mains filter
Fuses and cable cross-sections
8200 vector Mains Installation to EN 60204-1 Installation to UL
1)
FI
2)
Fuse L1, L2, L3, PE [mm
2
] Fuse L1, L2, L3, PE [AWG]
E82EV453K4B
3/PE AC 320 V - 0 % ... 550 V +0 %
M100 A 50 100 A 1
E82EV553K4B
5
z-
...
5
z+
DC 450 V -0 % ... 775 V +0 %
M125 A 50 125 A 0
≥
m
1)
Use UL-approved cables, fuses and fuse holders only. UL fuse: 500 ... 600 V, tripping characteristic ”H” or ”K5”
2)
All-current sensitive e.l.c.b.
Observe national and re gional regulations (e. g. VDE 0113, EN 60204)