Important codes for quick commissioning
8
Commissioning
8.6
L
8.6-2
EDS82EV903-1.0-11/2002
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0002*
s
uSEr
cont.
Parameter set
transf er using the
keypad
Use the keypad to transfer parameter sets
to other controllers.
During transfer the parameters cannot
be accessed via other channels!
.
Keypad ð Controller
All available parameter sets (PAR1 ... PAR4,
70 With function module Application-I/O, INTERBUS,
PROFIBUS-DP, LECOM-B, DeviceNet/CANopen
and FPAR1) are overwritten with the
corresponding keypad data
10 With all other function modules
C0002* Parameter set
Keypad ð PAR1 (+ FPAR1)
Overwrite selected parameter set and, if
s
uSEr
transf er using the
keypad
71 With function module Application-I/O, INTERBUS,
PROFIBUS-DP, LECOM-B, DeviceNet/CANopen
necessary, FPAR1 with the corresponding
keypad data
(cont.)
11 With all other function modules
Keypad ð PAR2 (+ FPAR1)
72 With function module Application-I/O, INTERBUS,
PROFIBUS-DP, LECOM-B, DeviceNet/CANopen
12 With all other function modules
Keypad ð PAR3 (+ FPAR1)
73 With function module Application-I/O, INTERBUS,
PROFIBUS-DP, LECOM-B, DeviceNet/CANopen
13 With all other function modules
Keypad ð PAR4 (+ FPAR1)
74 With function module Application-I/O, INTERBUS,
PROFIBUS-DP, LECOM-B, DeviceNet/CANopen
14 With all other function modules
Controller ð Keypad
All available parameter sets (PAR1 ... PAR4,
80 With function module Application-I/O, INTERBUS,
PROFIBUS-DP, LECOM-B, DeviceNet/CANopen
and FPAR1) are copied to the keypad
20 With all other function modules
Keypad ð Function module
Overwrite the module-specific parameter
40 Only with function module INTERBUS,
PROFIBUS-DP, LECOM-B, DeviceNet/CANopen
set FPAR1 only
Function module ð Keypad
Copy the module-specific parameter set
50 Only with function module INTERBUS,
PROFIBUS-DP, LECOM-B, DeviceNet/CANopen
FPAR1 only
C0002*
s
uSEr
(cont.)
Saving of own
settings
9 PAR1 ð Own settings You can save your own basic settings for a
controller (e.g. machine delivery status):
1. Ensure that parameter set 1 is active
2. Controller inhibit
3. S e t C0003 = 3, a cknowledge with
v
4. S e t C0002 = 9, a cknowledge with v,
to save your own basic settings
5. S e t C0003 = 1, a cknowledge with
v
6. Enable the controller .
C0002*
s
Loading/copying of
your own basic
Using this function, PAR1 can be copied to
parameter sets PAR2 ... PAR4
uSEr
settings
5 Own settings ð PAR1
Restorage of own basic setting in the
(cont.)
6 Own settings ð PAR2
selected parameter set
7 Own settings ð PAR3
8 Own settings ð PAR4
C0003* Non-volatile 1
0 ParameternotsavedinEEPROM Data loss after mains disconnection
v
parameter saving
1 Parameter always saved in EEPROM • Active after every mains connection
• Cyclic parameter changes via bus
module are not allowed.
3 Own settings saved in EEPROM The parameter set 1 saved as own basic
setting with C0002 = 9