Basic units in the power range 45 ... 55 kW
Connection of relay outputs K 1 and K2
6
Basic unit wiring
6.7
6.7.3
L
6.7-7
EDS82EV903-1.0-11/2002
Function Relay position set Message
(Lenze setting)
data
X1.3/K21 Relay output
normally-closed
contact
open not assigned
X1.3/K22 Mid position contact
5
X1.3/K24 Relay output -
normally-open
contact
closed not assigned
...
.
PES HF-shield end by PE connection through shield bracket.
)
))
) Note!
l For switching the control signals use shielded cables and
establish an HF shield termination by PE connection.
l For mains potential switching unshielded cables are sufficient.
l The service life of the relay depends on the type of load (ohmic,
inductive or capacitive) and the value of the switching capacity.
l The output message can be changed under C0409.
l If you use a function module application I/O:
– The relay is only active with application I/O as of version
E82ZAFAVx21.
(
((
( Stop!
If you control a holding brake at the motor with the relay output, a
spark suppressor must be used in case of DC switching:
l Universal spark suppressor for 24 V DC brake,
l 6-pole Lenze brake rectifier for 180 V/205 V DC brake.
Relay K2