9.2.2 AC Drive Prole
For control via AC drive prole, the parameters listed in the following can be mapped to net-
work registers.
Details
The mapping entry for the AC Drive control word is 0x400B0110.
The mapping entry for the AC Drive status word is 0x400C0110.
Detailed informaon on the data mapping can be found in the chapter of the correspond-
ing network.
AC drive control word
The AC Drive control word 0x400B:001 (P592.01) will only be processed if the network control
in 0x2631:037 (P400.37) has been acvated and the network is also acve as control source.
4Control source change-over ^ 345
Moreover, some bits in the AC drive control word are ignored if the bit 5 ("Acvate net-
work control") is not set. For details see the parameter descripon for 0x400B:001
(P592.01).
The following logic applies to bit 0 "Run forward (CW)" and bit 1 "Run reverse (CCW)":
Bit 0
"Run forward (CW)"
Bit 1
"Run reverse (CCW)"
Acon
0 0 Stopping with stop method set in 0x2838:003 (P203.03).
0↗1 (edge) 0 Run forward (CW)
0 0↗1 (edge) Run reverse (CCW)
0↗1 (edge) 0↗1 (edge) No acon / last acon is connued to be executed.
1 1
1 0
0 1
1↘0 (edge) 1 Run reverse (CCW)
1 1↘0 (edge) Run forward (CW)
For further details on the single bits, see the following parameter descripons:
Parameter Name / value range / [default seng] Info
0x400B:001
(P592.01)
Process input data: AC Drive control word
(Process data IN: AC control word)
0x0000 ... [0x0000] ... 0xFFFF
Mappable control word with bit assignment in compliance with Ether-
Net/IP™ AC drive prole.
Bit 0 Run forward (CW) Bits are only evaluated if bit 5 = "1".
For the exact logic, see the above truth table.
Bit 1 Run reverse (CCW)
Bit 2 Reset error (0-1 edge)
Bit 5 Acvate network control If bit 5 = "1" and 0x2631:037 (P400.37) = "Network control acve [114]":
All bits of the AC drive control word are evaluated.
If bit 5 = "0" or 0x2631:037 (P400.37) = "Not connected [0]":
Bit 0, 1, 12, 13, 14, 15 of the AC drive control word are not evaluated
(ignored).
Acve control source is the "Flexible I/O conguraon". 4Control
source change-over ^ 345
Bit 6 Acvate network setpoint 0 = the standard setpoint source selected in 0x2860:001 (P201.01) is
used.
1 = network setpoint is used.
Bit 12 Disable inverter Bits are only evaluated if bit 5 = "1".
Bit 13 Acvate quick stop
Bit 14 Deacvate PID controlling
Bit 15 Acvate DC braking
Conguring the network
Predened process data words
AC Drive Prole
193

Table of Contents

Other manuals for Lenze I51AE175F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze I51AE175F and is the answer not in the manual?

Lenze I51AE175F Specifications

General IconGeneral
BrandLenze
ModelI51AE175F
CategoryInverter
LanguageEnglish

Related product manuals