13.9.1 Example 1: Acvaon via command (only when disabled)
Acvaon method 0x4046 (P755.00) = "Via command (disable required) [0]":
Switches S3 and S4 serve to select the parameter set (see the following table).
Switch S2 acvates the change-over. Since the change-over is acvated with a rising edge,
a buon (normally-open contact) can be used instead of a switch.
Change-over is only possible if the motor is not started (switch S1 open).
Connecon plan funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1 S2 S3 S4
Switch S1 Run
Switch S2 Load parameter set
Switches S3 ... S4 Parameter set selecon:
S3 S4
O O Parameter set 1
On O Parameter set 2
O On Parameter set 3
On On Parameter set 4
Parameter Name Seng for this example
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:004 (P400.04) Reset fault Not connected [0]
0x2631:013 (P400.13) Reverse rotaonal direcon Not connected [0]
0x2631:018 (P400.18) Acvate preset (bit 0) Not connected [0]
0x2631:040 (P400.40) Load parameter set Digital input 2 [12]
0x2631:041 (P400.41) Select parameter set (bit 0) Digital input 3 [13]
0x2631:042 (P400.42) Select parameter set (bit 1) Digital input 4 [14]
0x2824 (P200.00) Control selecon Flexible I/O conguraon [0]
0x4046 (P755.00) Acvaon of parameter set Via command (disable required) [0]
t
t
t
t
t
t
t
t
t
t
t
1
2
3 4 3
Digital input 1 [11] Run
Digital input 4 [14]
Constant TRUE [1]
Digital input 3 [13]
Digital input 2 [12]
Mains voltage
Select par. set (bit 0)
Parameter set 4 active [111]
Parameter set 1 active [108]
Enable inverter
Parameter set 3 active [110]
Parameter set 2 active [109]
Output signals
Status signals
Active parameter set
Select par. set (bit 1)
Load parameter set
Input signals
FunctionTrigger
The status signals can be assigned to digital outputs. 4Conguraon of digital outputs ^ 415
The change-over is acvated with the "Load parameter set" funcon (FALSE/TRUE edge).
If the inverter is enabled and the motor is started, a change-over is not possible.
Flexible I/O conguraon
Funcons for parameter change-over
Example 1: Acvaon via command (only when disabled)
395

Table of Contents

Other manuals for Lenze I51AE175F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze I51AE175F and is the answer not in the manual?

Lenze I51AE175F Specifications

General IconGeneral
BrandLenze
ModelI51AE175F
CategoryInverter
LanguageEnglish

Related product manuals