6.2 Diagnoscs parameter
The inverter provides many diagnosc parameters which are helpful for operaon, mainte-
nance, error diagnosis, error correcon, etc.
In the following overview the most common diagnosc parameters are listed. For the key-
pad you can nd these diagnosc parameters in group 1.
Further parameters for more specic diagnosc purposes are described in the following
subchapters.
The diagnosc parameters can only be read and cannot be wrien to.
Parameter Name / value range / [default seng] Info
0x2030 CRC parameter set
Read only
Display of the 32-bit hash sum for the integrity check of the parameter
set.
0x2B0B Frequency setpoint
Read only: x.x Hz
From version 03.00
Display of the actual frequency setpoint that is internally transferred to
the motor control (aer scaling and ramp generator).
0x2B0E
(P102.00)
Frequency setpoint
(Freq. setpoint)
Read only: x.x Hz
Display of the frequency setpoint currently assigned.
Depending on the present operang condions, this value may dier
from the current output frequency 0x2DDD (P100.00).
0x2B0F VFC output frequency
Read only: x.x Hz
Display of the current output frequency at V/f operaon.
0x2D4F
(P123.00)
Motor ulisaon (i²*t)
(Mot. i2t ulis.)
Read only: x %
Display of the current thermal motor ulisaon.
0x2D87
(P105.00)
DC-bus voltage
(DC-bus voltage)
Read only: x V
Display of the current DC-bus voltage.
0x2D88
(P104.00)
Motor current
(Motor current)
Read only: x.x A
Display des present current-r.m.s. value.
0x2D89
(P106.00)
Motor voltage
(Motor voltage)
Read only: x VAC
Display of the current motor voltage.
0x2DA2:001
(P108.01)
Output power: Eecve power
(Output power: Eecve power)
Read only: x.xxx kW
Display of the acve output power for an energy analysis in the respec-
ve applicaon.
0x2DA2:002
(P108.02)
Output power: Apparent power
(Output power: Apparent power)
Read only: x.xxx kVA
Display of the apparent output power for an energy analysis in the
respecve applicaon.
0x2DA3:001
(P109.01)
Output energy: Motor
(Output energy: Motor)
Read only: x.xx kWh
Display of the output power in motor mode for an energy analysis in the
respecve applicaon.
0x2DA3:002
(P109.02)
Output energy: Generator
(Output energy: Generator)
Read only: x.xx kWh
Display of the output power in generator mode for an energy analysis in
the respecve applicaon.
0x2DDD
(P100.00)
Output frequency
(Output frequency)
Read only: x.x Hz
Display of the current output frequency for diagnoscs of the control.
0x400D
(P101.00)
Scaled actual value
(Scaled act value)
Read only: x Units
Display of the current speed in applicaon units.
0x6077
(P107.00)
Torque actual value
(Torque actual)
Read only: x.x %
Display of the current torque.
100 % ≡ Motor rated torque 0x6076 (P325.00)
0x6078
(P103.00)
Current actual value
(Current actual)
Read only: x.x %
Display of the present motor current.
100 % ≡ Motor rated current 0x6075 (P323.00)
Diagnoscs and fault eliminaon
Diagnoscs parameter
68

Table of Contents

Other manuals for Lenze I51AE175F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze I51AE175F and is the answer not in the manual?

Lenze I51AE175F Specifications

General IconGeneral
BrandLenze
ModelI51AE175F
CategoryInverter
LanguageEnglish

Related product manuals