11.17 Process data
This chapter describes addional funcons that provide process data for a higher-level Con-
troller.
11.17.1 Posion counter
This funcon counts the number of motor revoluons. The current counter content (actual
posion) can be output as process data value via network to implement a simple posion con-
trol in a higher-level Controller.
Precondions
The number of motor revoluons is reconstructed from the motor model. For this pur-
pose, the motor control type "Sensorless control (SL PSM) [3]" must be selected and set in
0x2C00 (P300.00). 4Sensorless control for synchronous motors (SL-PSM) ^ 125
The posion control must be implemented in the Controller.
Details
The signal source for the posion counter is selected in 0x2C49:001 (P711.01). The posion
counter can count forwards and backwards. The current counter content (actual posion) is
displayed in 0x2C49:003 (P711.03). Aer the maximum or minimum value has been reached,
an overow takes place.
Reset posion counter:
The posion counter is reset when the supply voltage is switched on.
The posion counter can be set manually via the "Posion counter reset" 0x2631:054
(P400.54) funcon or the NetWordIN1 0x4008:001 (P590.01) data word. For a reset via
NetWordIN1, the "Posion counter reset [54]" funcon must be assigned to a bit of the
data word. Depending on the selecon in 0x2C49:002 (P711.02), the reset can be made
either edge-controlled or status-controlled.
Parameter Name / value range / [default seng] Info
0x2631:054
(P400.54)
Funcon list: Posion counter reset
(Funcon list: PosCounter reset)
From version 03.00
For further possible sengs, see parameter
0x2631:001 (P400.01). ^ 351
Assignment of a trigger for the "Posion counter reset" funcon.
Trigger = FALSE-TRUE edge: Reset posion counter manually.
Trigger = FALSE: no acon.
Notes:
In 0x2C49:002 (P711.02) it can be selected whether the reset is to be
eected edge-controlled (default seng) or status-controlled.
0 Not connected
0x2C49:001
(P711.01)
Posion counter: Signal source
(Posion counter: Signal source)
From version 03.00
Selecon of the signal source for the posion counter.
0 Disbled Posion counter is deacvated.
5 Internal motor model The motor revoluons reconstructed from the internal motor model of
the sensorless control (SL PSM) are counted.
The counter content will not be updated if the power secon is
switched o.
Aer restarng the power secon, the counng of the last counter
content is connued.
0x2C49:002
(P711.02)
Posion counter: Reset mode
(Posion counter: Reset mode)
From version 03.00
Selecon if the manual reset of the posion counter is to be eected
edge-controlled or status-controlled.
0 Reset by rising edge
1 Reset by signal state true
0x2C49:003
(P711.03)
Posion counter: Actual posion
(Posion counter: Actual posion)
Read only
From version 03.00
Mappable parameter for providing the current counter content (actual
posion) via network.
Scaling (applies to every measuring method or encoder resoluon):
Upper 16 bits: Counted revoluons (0 ... 65535, overow possible)
Lower 16 bits: Current posion within the revoluon (0 ... 65535)
Addional funcons
Process data
Posion counter
321

Table of Contents

Other manuals for Lenze I51AE175F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze I51AE175F and is the answer not in the manual?

Lenze I51AE175F Specifications

General IconGeneral
BrandLenze
ModelI51AE175F
CategoryInverter
LanguageEnglish

Related product manuals