4.2.2.2 Fusing and terminal data
Fuse data
Inverter
I51AE125D
I51AE137D
I51AE155D
I51AE175D
I51AE211D
I51AE215D
I51AE222D
Cable installaon in compliance with EN 60204-1
Installaon method B2
operaon without mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 10 16 25
Circuit breaker
Characteriscs B
Max. rated current A 10 16 25
operaon with mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 10 16 25
Circuit breaker
Characteriscs B
Max. rated current A 10 16 25
Earth-leakage circuit breaker
1-phase mains connecon ≥ 30 mA, type A or B
3-phase mains connecon ≥ 30 mA, type B
Fuse data
Inverter I51AE125D
I51AE137D
I51AE155D
I51AE175D
I51AE211D
I51AE215D
I51AE222D
Cable installaon in compliance with US Naonal Electrical Code NFPA 70 / Canadian Electrical Code C22.1
operaon without mains choke
Fuse
Characteriscs all acc. to UL 248 / Class CC
Max. rated current A 15 30
Circuit breaker
Characteriscs -
Max. rated current A 15 30
operaon with mains choke
Fuse
Characteriscs all acc. to UL 248 / Class CC
Max. rated current A 15 30
Circuit breaker
Characteriscs -
Max. rated current A 15 30
Earth-leakage circuit breaker
1-phase mains connecon ≥ 30 mA, type A or B
3-phase mains connecon ≥ 30 mA, type B
Electrical installaon
Mains connecon
3-phase mains connecon 230/240 V
24