Electrical installaon
Operang Instrucons i550-Cabinet
5.3 Control terminals
Standard I/O
Input/output Terminal X3 Informaon
Digital inputs DI1, DI2, DI3, DI4, DI5 DI3/DI4 can be oponally used as frequency or encoder input.
HIGH-acve/LOW-acve switchable LOW = 0 ... +3 V,
HIGH = +12 V ... +30 V
Digital outputs DO1 Digital output (max. 100 mA for DO1 and 24-V output)
Analog inputs AI1, AI2 Can be oponally used as voltage input or current input.
Analog outputs AO1 Can be oponally used as voltage output or current output.
24-V input 24E Input for mains-independent power DC supply of control electronics
(including communicaon). Max. 1 A
10-V output 10 V Primarily for the supply of a potenometer (1 ... 10 kΩ).
Max. 10 mA
24-V output 24 V Primarily for the supply of digital inputs. (Max. 100 mA for DO1
and 24-V output)
Reference potenal GND
Connecon system Pluggable spring
terminal
Inverter [kW] 0.25 ... 132
Connecon Control terminals X3
Connecon type Pluggable spring terminal
Min. cable cross-secon mm² -
Max. cable cross-secon mm² 1.5
Stripping length mm 9
Tightening torque Nm -
Tools required 0.4 x 2.5
Control terminals
DC 24 V SELV/PELV
(+19.2 … +28.8 V)
1k ... 10k
0 ... 10 V
S1
DI3 DI4
24E
AI1
AI2
10V
GND
AO1
24V
X3
GND
GND
24E
DO1
DI1
DI2
DI3
DI4
DI5
Front
row
Back
row
5.5 PTC input
In the default seng, the motor temperature monitoring is acve! By default, a wire jumper
is installed between the terminals T1 and T2.
Before connecng a thermal sensor, remove the wire jumper.
Inverter [kW] 0.25 ... 132
Connecon PTC or thermal contact
X109
Terminal X109: T1
Terminal X109: T2
Sensor types PTC single sensor
PTC triplet sensor
Thermal contact
5.4 Relay output
The relay is not suitable for direct switching of an electromechanical holding brake.
Use a corresponding suppressor circuit in case of an inducve or capacive load.
Inverter [kW] 0.25 ... 132
Connecon Relay output X9
Connecon type Pluggable screw terminal
Min. cable cross-secon mm² -
Max. cable cross-secon mm² 1.5
Stripping length mm 6
Tightening torque Nm 0.2
Tools required 0.4 x 2.5
COM Common contact
NC Normally-closed contact
NO Normally-open contact
Max. switching voltage/switching
current
AC 240 V/3 A
DC 24 V/2 A
DC 240 V/0.16 A
PTC input
X109
T1
T2
Relay output
NC
NO
COM
X9
AC 240 V
3 A

Other manuals for Lenze i550 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i550 Series and is the answer not in the manual?

Lenze i550 Series Specifications

General IconGeneral
Protection ClassIP20
Ambient Temperature-10°C to +50°C
Overload Capacity150% for 60 seconds
Control TypeVector control
Communication InterfacesCANopen, Modbus, Ethernet, PROFIBUS, PROFINET
SafetySTO (Safe Torque Off)
Frequency Range0 Hz
Cooling MethodAir cooling
Storage Temperature Range-25°C to +70°C
Input Voltage Range3-phase 380...480 V AC -15%/+10%