SAFE OPERATION MODE
Allows the ice machine to operate up to 72 hours if the
ice thickness probe (E19 fault) and/or water level probe
sensors fail (E20 fault).
When the control board starts the safe mode an alert
is flashed on the LCD display to notify the end-user
they have a production problem.
The control board automatically initiates
and monitors the safe mode. The control will
automatically exit the safe mode if a normal signal is
received from the input.
After 72 hours the control board will enter a standby
mode and turn off
The control board needs a five cycle history to operate
safe mode. If five cycles have never been successfully
completed the ice machine will shut-off.
WATER ASSIST HARVEST
FIRMWARE VERSION 5.010 AND HIGHER
When the damper/curtain does not open within 3.5
minutes in the harvest cycle the following occurs:
3.5 minutes - The water inlet valve energizes until
water touches the high water level probe.
4 minutes - The water pump energizes.
6.5 to 7 minutes - The water dump valve energizes.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc Indigo ID0502A and is the answer not in the manual?

Manitowoc Indigo ID0502A Specifications

General IconGeneral
BrandManitowoc
ModelIndigo ID0502A
CategoryIce Maker
LanguageEnglish

Related product manuals