QF0400/QC0700/QF0800/QF2200/QF2300 OPERATIONAL PROBLEM CHECKLIST
Problem Possible Cause To Correct
Ice machine does not operate. No electrical power to the ice machine.
Replace the fuse/reset the breaker/turn on the
main switch/plug power cord into receptacle.
Control board fuse open.
ICE/OFF/CLEAN toggle switch set improperly. Move the toggle switch to the ICE position.
8-minute lockout has not expired.
Bin Level light will flash to indicate 8-minute
lockout has not expired. Refer to sequence of
operation.
Bin level sensor is disconnected or is
contacting the ice.
Connect bin level sensor or remove ice
contacting probe.
High Pressure Control is open.
Clean condenser, check fan motor, check high
pressure control operation.
Gear motor runs but compressor will not start.
Remote Condenser Only
Water reservoir is empty.
(Water must contact the water level probes to
start the compressor.)
Open water service valve or clean float valve
screen.
Water level probes out of position. Correct water level probe position.
Water float valve will not energize electrically. Replace coil.
No electrical power to condensing unit.
Replace the fuse/reset the breaker/turn on the
main switch.