Part Number 80-1230-9 10/10 23
Installation
Location of Ice Machine
The location selected for the ice machine must meet
the following criteria. If any of these criteria are not
met, select another location.
• The location must be indoors.
• The location must be free of airborne and other
contaminants.
• The air temperature must be at least 45°F (7°C),
but must not exceed 110°F (43°C).
• The water temperature must be at least 45°F
(7°C), but must not exceed 90°F (32°C).
• The location must not be near heat-generating
equipment or in direct sunlight.
• The location must be capable of supporting the
weight of the ice machine and a full bin of ice.
• The location must allow enough clearance for
water, drain and electrical connections in the rear
of the ice machine.
• The location must not obstruct airflow through or
around the ice machine. Refer to the chart below
for clearance requirements.
• RFC Condensing Units ONLY - Interconnecting
wiring (115/60/1 or 230/50/1) is required between
the ice machine and condensing unit to energize
the contactor coil.
• The ice machine must be protected if it will be
subjected to temperatures below 32°F (0°C).
Failure caused by exposure to freezing
temperatures is not covered by the warranty. See
“Removal from Service/Winterization”