28 Part Number 80-1230-9 10/10
CIRCUIT AMPACITY
The minimum circuit ampacity is used to help select
the wire size of the electrical supply. (Minimum circuit
ampacity is not the ice machine’s running amp load.)
The wire size (or gauge) is also dependent upon
location, materials used, length of run, etc., so it must
be determined by a qualified electrician.
Self Contained Air-Cooled
Ice
Machine
Voltage
Phase Cycle
Max. Fuse/
Circuit
Breaker
Total
Amps
SN012
SN020
115/1/60 15 10.3
230/1/50 15 4.6
QF0400
115/1/60 15 9.8
230/1/50 15 4.2
Ice
Machine
Voltage
Phase
Cycle
Max. Fuse/
Circuit
Breaker
Minimum
Circuit
Amps
SF0400/
SN0450
Air-Cooled
115/1/60 20 13.7
230/1/50 15 7.2
Water-Cooled
115/1/60 20 12.9
230/1/50 15 6.6
SF0600/
SN0650
Air-Cooled
115/1/60 20 16.2
230/1/50 15 7.0
Water-Cooled
115/1/60 20 15.5
230/1/50 15 6.7
Remote Air-Cooled
115/1/60 20 17.9
JC0495
Traditional Remote Condenser
115/60/1 NA 2.3