Part Number 80-1230-9 10/10 159
3. Remove bin level probe from ice chute and clean
with Manitowoc Ice Machine Cleaner and
Sanitizer. Rinse well with fresh water, reinstall and
monitor the Bin light.
4. Disconnect bin level probe wire from the control
board and place a jumper from the bin level
terminal to ground.
Control Board
Bin Level Light
Cause
Off
Bin level probe
needed cleaning.
Flashes Go to step 4.
Control Board
Bin Level Light
Cause
On Replace bin level probe.
Flashes
Reconfirm control board is not
in an 8-minute lockout. Repeat
steps 1 – 4, then replace
control board.